Rockwell Automation Publication 193-UM015D-EN-P - February 2015
325
Metering and Diagnostics
Chapter 8
When single or three phase (Parameter 176) is set to single phase, average current
is calculated as follows:
Average Current = (L1 C L2 Current) / 2
Table 393 - Average Current (Parameter 46)
L1 Percent FLA
L1 Percent FLA (Parameter 47) reports the L1 current in comparison to the
active Full Load Amps programmed in FLA (Parameter 171) and FLA2
(Parameter 177).
L1 Percent FLA = L1 Current / Full Load Amps
Table 394 - L1 Percent FLA (Parameter 47)
L2 Percent FLA
L2 Percent FLA (Parameter 48) reports the L2 current in comparison to the
active Full Load Amps programmed in FLA (Parameter 171) and FLA2
(Parameter 177).
L2 Percent FLA = L2 Current / Full Load Amps
Table 395 - L2 Percent FLA (Parameter 48)
Default Value
0.00
Minimum Value
0.00
Maximum Value
20000000.00
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
100
Units
Amps
Default Value
0.0
Minimum Value
0.0
Maximum Value
1000.00
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
10
Units
%
Default Value
0.0
Minimum Value
0.0
Maximum Value
1000.00
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
10
Units
%
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......