Publication CNET-IN002A-EN-P - December 2001
Install a ControlNet Coax Media System
3-21
Connect Devices
After terminating your segments, you connect your devices.
1.
Remove and save the tap’s dust cap (located on the straight or
right-angle connector).
2.
Connect the tap’s straight or right-angle connector to your
device.
Connect Programming Terminals Through the NAP
Use the ControlNet™ network access cable (1786-CP) to connect
a programming terminal to any intelligent device (i.e. workstation,
PLC
®
processor, or adapter) on a ControlNet link through the network
access port (NAP).
1.
Connect one end of the 1786-CP cable to the NAP on the front
of the ControlNet node.
To connect a
See
programming terminal through the NAP
repeater
ControlNet processor, adapter or programming terminal
via a communication interface
procedure below
If your node supports: Connect the tap’s straight or right-angle
connector:
non-redundant media
to the
channel A
connector on the device
(
channel
B is not used)
1
redundant media
•
from
trunk cable A
to
channel A
on the
your device
•
from
trunk cable B to
channel B
on the
your device
1 While both channels are active, Allen-Bradley recommends using channel A for non-redundant
media.
Summary of Contents for Allen-Bradley ControlNet 1786 Series
Page 1: ...ControlNet Coax Media Planning and Installation Guide 1786 series Installation Instructions...
Page 6: ...Publication CNET IN002A EN P December 2001 4 Notes...
Page 60: ...Publication CNET IN002A EN P December 2001 3 24 Install a ControlNet Coax Media System Notes...
Page 70: ...Publication CNET IN002A EN P December 2001 4 Index...
Page 73: ......