Rockwell Automation Publication 1512A-UM101B-EN-P - December 2021
39
Chapter
4
Common Installation
Bus Splicing
Power Bus
1. The power and ground bus splice kit can be found in a package mounted
to the front of the shipping skid.
2. See
Access to the Power Bus on page 17
for standard enclosure and
for ArcShield™ enclosure.
3. For a
1200 A
power bus, assemble the splice bars as shown in
. Tighten the nuts to 45 lb•ft (61 N•m).
For a
2000 A
power bus, assemble the splice bars as shown in
. Tighten the nuts to 45 lb•ft (61 N•m).
For a
3000 A
power bus, assemble the splice bars as shown in
. Tighten the nuts to 45 lb•ft (61 N•m)
ATTENTION:
This procedure requires contact with medium voltage
components. To avoid shock hazards, lock out incoming power
before working on the equipment (See
). Verify with a hot stick or appropriate voltage measuring
device that all circuits are voltage free. Failure to do so may result in
severe burns, injury, or death.
IMPORTANT
Verify that the structure series numbers on the splice kit
package match the structure series number found on the
cabinet nameplate (See
Starter Identification on page 9
for details regarding the nameplate).
IMPORTANT
Attach the bus links to the cabinet on the left side first - as
viewed from the front of the unit.
IMPORTANT
Always place the bus clamps on the rear side of each main
horizontal bus or splice bar, as viewed from the front of
the unit (see