56
Rockwell Automation Publication 2100-IN012D-EN-P - September 2010
Chapter 4
Installing and Removing Plug-in Units
For the CENTERLINE 2100 MCC units with swing-out door latches,
you will need to rotate the latch bracket 90
o
clockwise to avoid interference
with the unit.
9.
Remove the unit from the MCC.
10.
Carefully install protective caps or close the manual shutters after unit is
removed.
Automatic shutters will close as units are removed.
11.
See the next section for additional information.
ATTENTION:
Plug-in MCC units may be heavy or awkward to handle. Use
an assistant or a platform lift device if necessary to help you handle the
unit.
ATTENTION:
All covers and doors must be in place before
applying power to the MCC. If units are removed, they must be
replaced with the appropriate items such as units, doors, and unit
support pans.
ATTENTION:
All covers and doors must be in place before
applying power to the MCC. If units are removed, they must be
replaced with the appropriate items such as units, doors, and unit
support pans.
When installing units for CENTERLINE 2100 Motor Control Centers
with the ArcShield rating, you must make sure you are installing a
unit that has the same arc resistance rating as the MCC in which it is
being installed. The arc resistance rating can be found on the
ArcShield label on the vertical wireway door.
Units that are not rated for 100 ms arc duration must not be installed
in a section that is rated for 100 ms arc duration. The arc resistant
rating will not apply if that is done.
Swing-out
Latch
Bracket