Industrial Performance Monitors
13
Rockwell Automation Publication 6186M-IN002C-EN-P - December 2011
Mounting Guidelines
Observe these guidelines when installing the monitor in a panel:
•
Confirm that there is adequate space behind the panel.
–
Allow a minimum of 51 mm (2.0 in.) around the back, sides, and bottom, and
77 mm (3.0 in.) on the top for ventilation.
–
A cabinet with a minimum depth of 112 mm (4.4 in.) is sufficient.
•
Cut supporting panels to specifications before installation. Take precautions so metal
cuttings do not enter components already installed in the panel.
•
Supporting panels must be at least 14 gauge to be sure of proper sealing against water and
dust and to provide proper support. The mounting hardware supplied accommodates
panels up to 6.0 mm (0.236 in.) thick.
•
Precautions should be made to assure that the operating temperatures, or other
environmental specifications of the monitor are followed both inside and outside of the
enclosure.
Panel Cutout Dimensions
The table lists the panel cutout dimensions for each monitor. Use the full-size template shipped
with each monitor to mark the cutout dimensions.
ATTENTION:
Failure to follow these guidelines may result in personal injury or damage to the
panel components.
Monitor Model
Cutout Dimensions, Approx. (H x W)
1200M
238.0 x 318.0 mm (9.37 x 12.51 in.)
1500M
285.6 x 386.6 mm (11.24 x 15.22 in.)
1700M
329.5 x 424.0 mm (12.97 x 16.69 in.)
1900M
363.5 x 449.6 mm (14.31 x 17.70 in.)