Bulletin 513 Combination Starter, Size 0-2
Bulletin 598 Empty Enclosure, Size 0-2
2
Publication
513-IN006F-EN-P - October 2017
40050-226-01
DIR 40050-226
(Version 06)
Wiring:
A number of openings are provided in the base for power and control wiring as well as for accessories. See illustrations above. Location and quantity
of the various accessories will determine the openings available for wiring.
Openings 1 and 4 are supplied with 1-1/2" (38 mm) pipe plugs while openings 2 and 5 are supplied with 3/4" (19 mm) pipe plugs.
Openings 3 and 6 are shipped with red plastic cap plugs. These openings are generally used for power and control wiring. If not used they must be
closed with 1-1/2" (38 mm) pipe plugs.
Wiring of electrical equipment or any other accessory is to be done in accordance with instructions furnished with the equipment and applicable
codes and laws.
To comply with the NEC, CEC, IEC and ATEX Directives and to prevent the passage of gasses, vapors or flames from one portion of the electrical
installation to another, conduit openings must be sealed with an appropriate sealing fitting. For use with metallic conduit only.
Mounting of a Unilock enclosure:
Mounting straps are provided on the rear of the enclosure for ease of mounting. The Unilock enclosure may be mounted to any solid surface capable
of supporting it’s weight by using 3/8" (9.5 mm) diameter screws or bolts.
Exterior dimensions of the Unilock enclosure are shown on sheet 3.