background image

Four holes for 3/8" (9.5mm)
dia. mounting screws

Disconnecting device
operating handle in
“OFF” position

Coupling latch

Locking attachment
(Shown in the locked position)

Hole for lock

Nut and lock washer
(Locking attachment removed for clarity)

T-Bolt

Installation Instructions

Bulletin 513 Combination Starter, Size 0-2

Bulletin 598 Empty Enclosure, Size 0-2

When it is desired to remove or replace the enclosure cover, the following recommended procedures should be observed.

Removing the enclosure cover:

Swing back locking attachment on the V-Band. Loosen nut on the T-Bolt of the V-Band to permit the coupling latch to be disengaged from the head of
the T-Bolt. Pull out coupling latch from the head of the T-Bolt. Spread V-Band and place over the enclosure base, thereby freeing the cover for removal.
Remove enclosure cover and place on a flat stable surface with the opening up.

CAUTION:  

Avoid any damage to flange surfaces as this could affect enclosure’s suitability for use in hazardous atmospheres.

Replace the enclosure cover:

Before replacing enclosure cover, clean base and cover flanges with a soft cloth. Looking at the cover front in the upright position (nameplate in
readable position), place operating handle in the downward or “OFF” position. Leave in “OFF” position for maximum safety. Align ribs inside the cover
with positioning channels on the mounting plates.

CAUTION:  

The upright position of the cover and base plus proper positioning channel alignment are very important. Failure to observe these directions may cause 

over jamming and equipment damage.

Slide cover toward base until the positioning pins in the base nearly enter the holes in the cover. At this point, when a disconnecting means is provided,
the external operating handle should be lifted slightly so that the circuit breaker operating slide mechanism becomes engaged with the roller. Continue
sliding cover toward base until the base and cover flanges meet. Install V-Band over the flanged joint and slide the T-Bolt into the coupling latch with
the tightening nut to the right.

CAUTION:  

Tighten the 3/8" (9.5) x 16 T-Bolt nut securely to provide proper enclosure sealing. NOTE: As a minimum, the helical spring lock washer beneath the nut 

must be fully compressed (65 lb-in/7.3 N•m). The maximum torque applied to the nut should not exceed 125 lb-in/14.1 N•m.

Press locking attachment over the bolt and nut, and insert lock (when used) into the hole in the locking attachment.

WARNING:  

To prevent electrical shock, disconnect from power source before  installing  or  servicing.  Keep free from contaminants.

Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice. In case of malfunction or 
damage, no attempts at repair should be made.  The product should be returned to the manufacturer for repair.  Do not dismantle the product. 

Summary of Contents for Allen-Bradley 513

Page 1: ...ng plates CAUTION The upright position of the cover and base plus proper positioning channel alignment are very important Failure to observe these directions may cause over jamming and equipment damage Slide cover toward base until the positioning pins in the base nearly enter the holes in the cover At this point when a disconnecting means is provided the external operating handle should be lifted...

Page 2: ...shipped with red plastic cap plugs These openings are generally used for power and control wiring If not used they must be closed with 1 1 2 38 mm pipe plugs Wiring of electrical equipment or any other accessory is to be done in accordance with instructions furnished with the equipment and applicable codes and laws To comply with the NEC CEC IEC and ATEX Directives and to prevent the passage of ga...

Page 3: ... 1 4 184 2 mm Mounting 5 7 8 149 2 mm 11 3 4 298 4 mm Mounting Four 3 8 9 5 mm Mounting screws 6 7 16 163 5 mm 8 1 16 204 8 mm 3 5 8 92 1 mm 3 Publication 513 IN006F EN P October 2017 40050 226 01 DIR 40050 226 Version 06 Bulletin 513 Combination Starter Size 0 2 Bulletin 598 Empty Enclosure Size 0 2 ...

Page 4: ...demarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Publication 513 IN006F EN P October 2017 Rockwell Automation maintains current product environmental information on its website at http www rockwellautomation com rockwellautomation about us sustainability ethics product environmental compliance page ...

Reviews: