Publication 193-UM010A-EN-P – January 2008
3-10
PROFIBUS Configuration
I/O Setup Group
OutA Pr FltState
Index No.
22
This parameter, in conjunction with parameter 23,
defines how Output A will respond when a trip occurs.
When set to “1”, Output A will continue to operate as
commanded via the network. When set to “0”, Output A
will open or close as determined by the setting of
parameter 23.
Access Rule
Read/Write
Size
1 byte
Group
I/O Setup
Units
—
Min. Value
0 = Go To FltValue (#23)
Max. Value
1 = Ignore Fault
Default Value
0
OutA Pr FltValue
Index No.
23
This parameter determines the state that Output A assumes
when a trip occurs and Parameter 22 is set to “0”.
Access Rule
Read/Write
Size
1 byte
Group
I/O Setup
Units
—
Min. Value
0 = Open
Max. Value
1 = closed
Default Value
0
OutA Pb FltState
Index No.
24
This parameter, in conjunction with Parameter 25,
defines how Output A will respond when a PROFIBUS
network fault occurs. When set to “1”, Output A will
hold the state prior to PROFIBUS fault occurrence. When
set to “0”, Output A will open or close as determined by
the setting of Parameter 25.
Access Rule
Read/Write
Size
1 byte
Group
I/O Setup
Units
—
Min. Value
0 = Go To FltValue (#25)
Max. Value
1 = Hold Last State
Default Value
0
OutA Pb FltValue
Index No.
25
This parameter determines the state that Output A assumes
when a PROFIBUS network fault occurs and Parameter 24 is
set to “0”.
Access Rule
Read/Write
Size
1 byte
Group
I/O Setup
Units
—
Min. Value
0 = Open
Max. Value
1 = Closed
Default Value
0
OutA Pb IdlState
Index No.
26
This parameter, in conjunction with parameter 27,
defines how Output A will respond when the PROFIBUS
network is idle. When set to “1”, Output A will hold the
state prior to PROFIBUS fault occurrence. When set to
“0”, Output A will open or close as determined by the
setting in Parameter 27. The Pb Flt parameters
supersede the Pb Idl parameters.
Access Rule
Read/Write
Size
1 byte
Group
I/O Setup
Units
—
Min. Value
0 = Go To IdlValue (#27)
Max. Value
1 = Hold Last State
Default Value
0