Rockwell Automation Publication 1794-IN049E-EN-P - May 2022

3

FLEX I/O 2-input Frequency Modules Installation Instructions

Environment and Enclosure

ATTENTION: 

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN/IEC 60664-1), at 

altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such 

environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific 

environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The 

enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be 

approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this 

publication may contain more information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 

1770-4.1

, for additional installation requirements.

• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.

WARNING: 

If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location 

installations. Be sure that power is removed or the area is nonhazardous before proceeding.

WARNING: 

If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous 

location installations. Be sure that power is removed or the area is nonhazardous before proceeding

ATTENTION: 

Personnel responsible for the application of safety-related Programmable Electronic Systems (PES) shall be aware of the safety 

requirements in the application of the system and shall be trained in using the system

ATTENTION: 

Do not remove or replace a Terminal Base unit while power is applied. Interruption of the backplane can result in unintentional operation or 

machine motion.

ATTENTION: 

This product is grounded through the DIN rail to chassis ground. Use zinc-plated chromate-passivated steel DIN rail to assure proper 

grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper 

or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to 

ground the DIN rail properly. See the Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 

1770-4.1

, for more 

information.

Prevent Electrostatic Discharge

ATTENTION: 

This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these 

guidelines when you handle this equipment:

• Touch a grounded object to discharge potential static.

• Wear an approved grounding wriststrap.

• Do not touch connectors or pins on component boards.

• Do not touch circuit components inside the equipment.

• Use a static-safe workstation, if available.

• Store the equipment in appropriate static-safe packaging when not in use.

ATTENTION: 

To reduce susceptibility to noise, power analog modules and digital modules from separate power supplies. Do not exceed a total length of 

9.8 ft (3 m) for DC power cabling.

Summary of Contents for Allen-Bradley 1794-IJ2

Page 1: ...Hazardous Location Approval 4 North American Hazardous Location Approval 4 Install Your Frequency Input Module 5 Connecting Wiring for the 1794 TB3G and 1794 TB3GS Terminal Base Unit 5 Resolution and...

Page 2: ...documenti elencati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installa...

Page 3: ...s nonhazardous before proceeding WARNING If you connect or disconnect wiring while the field side power is on an electrical arc can occur This could cause an explosion in hazardous location installati...

Page 4: ...ust be used only with ATEX IECEx certified Rockwell Automation backplanes Secure any external connections that mate to this equipment by using screws sliding latches threaded connectors or other means...

Page 5: ...d evenly to seat the module in the terminal base unit The module is seated when the latching mechanism 7 is locked into the module Connecting Wiring for the 1794 TB3G and 1794 TB3GS Terminal Base Unit...

Page 6: ...annel 1 A 11 A 12 A 7 A 5 A 3 A 8 A 10 A 12 6V AC Vortex A 2 A 1 A 3 A 13 A 14 A 12 3V AC Vortex A 2 A 0 A 3 A 13 A 15 A 12 Gate 24V DC IEC 1 Proximity 3 4 B 24 B 23 B 20 B 25 B 26 B 29 24V DC Contact...

Page 7: ...1 8 0 0002 200 0 0002 0 0225 0 0227 0 1 0 7 1 7 0 0001 500 0 00008 0 0225 0 02258 0 1 0 7 1 7 0 00004 1000 0 00004 0 0225 0 02254 0 1 0 7 1 7 0 00002 Table 2 Input Map Bit 15 14 13 12 11 10 09 08 07 0...

Page 8: ...module is in a Faulted condition internal error Table 3 Output Map Dec 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Oct 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 0 CF SSM FR CH 0 Number of pulses to terminate...

Page 9: ...Logic Drive On Status OK Off Dark 24V Power Turned Off or 5V Logic Power Problem Solid Green Module OK Normal Operating Mode Solid Red Module Fault Outputs Disabled Table 5 Diagnostic Bit Definition...

Page 10: ...re off detection 0 4 mA for proximity encoder or contact switch with 50 k shunt resistor Frequency input impedance 5 k for 50 mV Extended Magnetic Pickup 5 k for 500 mV Magnetic Pickup 10 k for 3V Vor...

Page 11: ...0 1 2 yellow status indicators Out 0 Out 1 logic side Keyswitch Position 1 Wire size Determined by installed terminal base Wiring category 1 2 on signal ports 3 on power ports Wire type Shielded on s...

Page 12: ...ents EN 60079 15 Potentially Explosive Atmospheres Protection n II 3 G Ex nA IIC T4 Gc DEMKO 14 ATEX 1342501X IECEx IECEx System compliant with IEC 60079 0 General Requirements IEC 60079 15 Potentiall...

Page 13: ...Rockwell Automation Publication 1794 IN049E EN P May 2022 13 FLEX I O 2 input Frequency Modules Installation Instructions Notes...

Page 14: ...be collected separately from any unsorted municipal waste Rockwell Automation Support Use these resources to access support information Documentation Feedback Your comments help us serve your documen...

Reviews: