FLEX I/O AC Digital Input Modules
15
Publication 1794-IN102C-EN-P - July 2015
For example, to increase the off-to-on filter time to 12 ms for all inputs at address rack 1,
module group 0, set bits and program as shown below.
To increase the filter time, set the bits according to the Input Filter Time table.
Input Filter Time
Bits
Description
Selected
Filter Time
Maximum
Filter Time
(ms)
1794-IA8
Maximum
Filter Time
(ms)
1794-IA8I
Maximum
Filter Time
(ms)
1794-IA16
02
01
00
Filter Time –
inputs 00...11
Off
to
On
On
to
Off
Off
to
On
On
to
Off
Off
to
On
On
to
Off
05
04
03
Filter Time –
inputs 12...15
0
0
0
Filter Time 0 (Default)
256
μ
s
8.4
26.4
8.4
26.4
7.5
26.5
0
0
1
Filter Time 1
512
μ
s
8.6
26.6
8.6
26.6
8
27
0
1
0
Filter Time 2
1 ms
9
27
9
27
9
28
0
1
1
Filter Time 3
2 ms
10
28
10
28
10
29
1
0
1
Filter Time 4
4 ms
12
30
12
30
12
31
1
0
1
Filter Time 5
8 ms
16
34
16
34
16
35
1
1
0
Filter Time 6
16 ms
24
42
24
42
24.5
44
1
1
1
Filter Time 7
32 ms
40
58
40
58
42
60.5
1
0
0
7
6
5
4
3
FLL
I:000
00
Fill File
Source
Destination
Length
#O:010
1
Write FT to complement
of input module.
Write filter time on system startup.
7
6
5
4
3
2
1
0
0
1
0
= 4 Octal or 4 Decimal
2
1
0
= 44 Octal or 36 Decimal
0
1
0
1
0
0
1794-IA8
1794-IA16
1794-IA8I