58
Rockwell Automation Publication 1790-UM001B-EN-P - April 2021
Appendix A Install, Wire, and Configure PROFIBUS Modules
9. Set the Watchdog Time Base and Current Range.
10. Save the configuration file.
Download the Configuration
To download the configuration to the module, follow these steps:
1. Make sure that the serial communication cable is connected between the
PC com port and the scanner serial port.
2. Verify that the processor is in Program mode.
3. Use the SST PROFIBUS configuration tool to connect to the master.
A. Click the SLC
Addresses tab.
B. Choose the Input.
This example uses
the I Type input.
A. Click the Ext. Prms tab.
B. Use the pull-down menu
to change the Watchdog
Time Base.
C. Use the pull-down menu to
change the Current Range.
D. Click OK when finished.
A. Right-click the master to
see the pull-down menu.
B. Click Connect.