10
Rockwell Automation Publication 1790-UM001B-EN-P - April 2021
Chapter 1 Overview
The output module provides two single-ended analog output channels, either
voltage or current, depending on the module selected.
lists the CompactBlock LDX I/O module types and corresponding
operating ranges:
Each analog base module supports up to two CompactBlock LDX I/O discrete
expansion modules.
Hardware Features
The modules contain either removable D-shell connectors or fixed terminal
blocks. The CompactBlock LDX I/O module four input channels are single-
ended. The CompactBlock LDX I/O module two output channels are also
single-ended. Module configuration is normally done via the controller’s
programming software. In addition, some controllers support configuration
via the user program.
shows the CompactBlock LDX I/O analog module hardware features.
Figure 1 - Hardware Features
General Diagnostic Features
The CompactBlock LDX I/O modules contain diagnostic features that can help
you identify the source of problems that may occur during power-up or during
Table 1 - CompactBlock LDX I/O Module Types and Operating Ranges
CompactBlock LDX I/O Module
Type:
Operating Range:
1790D-N4CO
1790D-TN4CO
Current input
4…20 mA
or
0…20 mA
1790D-NOC2
1790D-TNOC2
Current output
0…20 mA
1790D-TN4VO
Voltage input
0…10V DC
1790D-TNOV2
Voltage output
0…10V DC
DIN rail slot
DeviceNet
network
connector
Panel
mount
hole
Analog I/O
connections (D-
shell shown)
Panel mount hole
Node address switches
Expansion connector
under cover
Module
indicators