Publication 1769-UM002B-EN-P - July 2005
4-24
Module Data, Status, and Channel Configuration for the Output Modules
1769-OF8C and -OF8V Channel Configuration
The first two words of each eight word group in the configuration file allow
you to change the parameters of each channel independently. For example,
words 8 and 9 correspond to channel 1 while words 56 and 57 correspond to
channel 7.
Table 4.12 1769-OF8C Channel Configuration
(1)
Define
Indicate this
These bit settings
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Program (Idle) to
Fault Enable
Program (Idle)
Mode Data
Applied
(2)
0
Fault Mode
Data Applied
1
Hold for
Initialization
Disabled
0
Enabled
1
Program (Idle)
Mode
Hold Last
State
0
User-Defined
Value
1
Fault Mode
Hold Last
State
0
User-Defined
Fault Value
1
Enable Ramping
Disabled
0
Enabled
1
Enable Clamp/
Alarm Latching
Disabled
0
Enabled
1
Enable High
Clamp/ Alarm
Interrupt
Disabled
0
Enabled
1
Enable Low
Clamp/ Alarm
Interrupt
Disabled
0
Enabled
1
Enable Channel
Disabled
0
Enabled
1
(1)
Refer to the 1769-OF8C and -OF8V Output Channel Configuration table.
(2)
These functions are not supported by all controllers (e.g. MicroLogix 1500) using any configuration method. Refer to your
controller manual for details.
Summary of Contents for Allen-Bradley 1769-IF4
Page 1: ...CompactI OAnalog Modules 1769 IF4 IF8 OF2 OF8C and OF8V User Manual ...
Page 4: ...Publication 1769 UM002B EN P July 2005 Summary of Changes 2 Notes ...
Page 10: ...Publication 1769 UM002B EN P July 2005 Table of Contents vi ...
Page 14: ...Publication 1769 UM002B EN P July 2005 4 Notes ...
Page 183: ......