142
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Chapter 8
Replacing POINT Guard I/O Modules
controller to download the proper module configuration, and re-establish the
safety connection.
Scenario 1 - Replacement Module Is Out-of-box and Safety Signature Exists
1.
Remove the old I/O module and install the new module.
2.
Right-click the replacement POINT Guard I/O module and choose
Properties.
3.
Click
to the right of the safety network number to open the Safety
Network Number dialog box.
4.
Click Set.
Table 11 - Replacing a Module
GuardLogix Safety
Signature Exists
Replacement
Module Condition
Action Required
No
No SNN
(Out-of-box)
None. The module is ready for use.
Yes or No
Same SNN as original
safety task
configuration
None. The module is ready for use.
Yes
No SNN
(Out-of-box)
See
Scenario 1 - Replacement Module Is Out-of-box and Safety
.
Yes
Different SNN from
original safety task
configuration
See
Scenario 2 - Replacement Module SNN Is Different from Original
and Safety Signature Exists on page 143.
No
Scenario 3 - Replacement Module SNN Is Different from Original
Summary of Contents for Allen-Bradley 1734-IB8S
Page 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Page 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Page 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Page 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Page 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Page 211: ......