All parameters are specified at 12V, 4.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM015A-EN-P — March 2014

3

Bulletin 1606 Switched Mode Power Supplies

1. Intended Use

This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office, 
communication, and instrumentation equipment.

Do not use this power supply in equipment where malfunction may cause severe personal injury or threaten human life.

2. Installation Requirements

This device may only be installed and put into operation by qualified personnel.

This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.

Should damage or malfunction occur during installation or operation, immediately turn power off and send unit to the factory for inspection.

Mount the unit on a DIN rail so that the terminals are located on the bottom of the unit. For other mounting orientations, refer to derating 
requirements in this document.

This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid 
(e.g. cable conduits) by more than 30%!

Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the 
device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat 
source (e.g. another power supply).

SHOCK HAZARD: 

 

Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input 

block for earth connection and not one of the screws on the housing.

- Turn power off before working on the device. Protect against inadvertent re-powering

- Make sure that the wiring is correct by following all local and national codes

- Do not modify or repair the unit

- Do not open the unit as high voltages are present inside

- Use caution to prevent any foreign objects from entering the housing

- Do not use in wet locations or in areas where moisture or condensation can be expected

- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.

WARNING: 

 EXPLOSION HAZARDS! 

Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless 
power has been switched off or the area is known to be non-hazardous.

Summary of Contents for Allen-Bradley 1606-XLP60BQ

Page 1: ...Sealed Enclosure 21 20 12 Mounting Orientations 22 Bulletin 1606 Switched Mode Power Supplies Catalog Number 1606 XLP60BQ Index PE and symbol PE is the abbreviation for Protective Earth and has the sa...

Page 2: ...he public mains network or exposed to a critical industrial environment The XLP family of power supplies offers output voltages from 5 to 56Vdc and power ratings from 15 to 120W Specification Quick Re...

Page 3: ...ot require an external fan Do not obstruct airflow and do not cover ventilation grid e g cable conduits by more than 30 Keep the following installation clearances 40mm on top 20mm on the bottom 5mm on...

Page 4: ...see Fig 3 2 Rise time typ 40ms 40ms 50ms at 12V 4 5A 0mF see Fig 3 2 100ms 90ms 110ms at 12V 4 5A 4 5mF Turn on overshoot max 200mV 200mV 200mV see Fig 3 2 The power factor is the ratio of the true or...

Page 5: ...endent The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V Inrush current max 17Apeak 21Apeak 40Apeak 40 C ambient col...

Page 6: ...output voltage which can occur at the clockwise end position of the potentiometer due to tolerances There is no guarantee this value can be achieved The typical value is about 15 8V Fig 5 1 Output vol...

Page 7: ...ld up Time Zero Transition Output Voltage Input Voltage 7 DC Input The power supply can also be supplied from a DC source Use a battery or similar DC source For other sources contact RA Connect the po...

Page 8: ...lf load typ 10 6W 9 3W 7 9W at 12V 4 5A full load Fig 8 1 Efficiency vs output current at 12V typ Fig 8 2 Losses vs output current at 12V typ Efficiency 0 80 84 88 78 90 4 5A 0 5 2 5 2 1 5 82 86 b c a...

Page 9: ...miter Power Converter Output Voltage Regulator Output Filter VOUT DC on PE 10 Front Side and User Elements Fig 10 1 Front side A Output Terminals Screw terminals Dual terminals for the negative and po...

Page 10: ...such as electrolytic capacitors has been reduced AC 100V AC 120V AC 230V Lifetime expectancy 34 000h 41 000h 56 000h at 12V 4 5A and 40 C 180 000h 181 000h 128 000h at 12V 2 25A and 40 C 95 000h 115 0...

Page 11: ...A Voltage interruptions EN 61000 4 11 0Vac 5000ms Criterion C Input voltage swells RA internal standard 300Vac 500ms Criterion A Powerful transients VDE 0160 over entire load range 750V 1 3ms Criteri...

Page 12: ...0m 6 560 to 20 000ft reduce output power or ambient temperature see Fig 14 2 IEC 62103 EN 50178 overvoltage category II Altitude de rating 4W 1000m or 5 C 1000m 2000m 6500ft see Fig 14 2 Over voltage...

Page 13: ...protection 2 5mm in diameter e g screws small parts Over temperature protection not included Input transient protection MOV Metal Oxide Varistor Internal input fuse T3 15A H B C not user replaceable...

Page 14: ...wn Connect all phase terminals together as well as all output poles before conducting the test When testing set the cut off current settings to the value in the table below Fig 17 1 Dielectric strengt...

Page 15: ...0950 1 RECOGNIZED E168663 for use in the U S A UL 60950 1 and Canada C22 2 No 60950 Information Technology Equipment Level 3 NEC Class 2 NEC CLASS 2 Listed as Limited Power Source LPS in the UL 60950...

Page 16: ...2014 Bulletin 1606 Switched Mode Power Supplies 19 Physical Dimensions and Weigth Weight 250g 0 55lb DIN Rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm The DIN...

Page 17: ...built in large sized output capacitors inside the power supply can deliver extra current Discharging this capacitor causes a voltage dip on the output The following two examples show typical voltage...

Page 18: ...nal fuse is necessary or utilized minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker A minimum value of 10A B or 6A C Characteristic breaker should be used 20...

Page 19: ...t is allowed as long as the average output current through one terminal pin does not exceed 25A If the current is higher use a separate distribution terminal block Fig 20 3 Daisy chaining of outputs F...

Page 20: ...urrent EMI inrush current and harmonics all increase when using multiple power supplies Earth Unit A AC DC Unit B AC DC Load 20 9 Operation on Two Phases 240V 10 max Fuse L2 L1 L3 L N PE Power Supply...

Page 21: ...ent results can be used as a reference to estimate the temperature rise inside the enclosure The power supply is placed in the middle of the box no other heat producing items are inside the box Enclos...

Page 22: ...current Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 20 7 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Output Power 0 1...

Page 23: ......

Page 24: ...ial help in getting your product up and running New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manuf...

Reviews: