Rockwell Automation Publication 1606-RM101A-EN-P - July 2020
15
Wiring Instructions
1. Use appropriate copper cables that are designed for minimum operating
temperatures of:
• 60 °C (140 °F) for ambient up to 45 °C (113 °F)
• 75 °C (167 °F) for ambient up to 60 °C (140 °F)
• 90 °C (194 °F) for ambient up to 70 °C (158 °F)
2. Follow national installation codes and installation regulations.
3. Ensure that all strands of a stranded wire enter the terminal connection.
4. Securely tighten unused terminal compartments.
5. Ferrules are allowed.
Daisy Chaining
Daisy chaining (jumping from one power supply output to the next) is allowed
for catalog numbers: 1606-XLE240E, -XLE240EC, -XLE240EP, and -XLE240EL.
Daisy chaining is not allowed for 1606-XLE240EH.
Daisy chaining is allowed as long as the average output current through one
terminal pin does not exceed 25 A. If the current is higher, use a separate
distribution terminal block as shown in
Functional Diagram
Figure 20 - Functional Diagram
Figure 18 - Daisy Chaining of Outputs
Figure 19 - Using Distribution Terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
max 25 A
continuous
Distribution
Terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
+
+
-
-
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Input Fuse
Input Filter
Input Rectifier
Inrush Current Limiter
V
OUT
L
N
DC-ok
Contact
DC-ok
LED
DC-ok
Relay
-