Physical Dimensions and 
Weight

Attributes

Values and Descriptions

Width

36 mm  ( 1.42 in.)

Height

90 mm  ( 3.54 in.)

Depth

91 mm  ( 3.58 in.)
The DIN rail height must be added to the unit depth to calculate the total required 
installation depth.

Weight

270 g (0.6 lb)

DIN rail

Use 35 mm (1.38 in.) DIN rails according to EN 60715 or EN 50022 with a height of 7.5 mm 
(0.295 in.) or 15 mm (0.59 in.).

Housing material

High-grade polycarbonate/ ABS blend material

Installation clearances

Keep the following min installation clearances: 
• 40 mm (1.57 in.) on the top
• 20 mm (0.79 in.) on the bottom
• 0 mm (0 in.) on the left side
• 0 mm (0 in.) on the right side
• If the adjacent device is a heat source, increase the side clearances from 0 mm 

(0 in.) to 15 mm (0.59 in.).

Penetration protection

Small parts like screws and nuts with a diameter larger than 4.2 mm (0.165 in.).

Figure 22 - Front View

Figure 23 - Side View

 

All dimensions in mm 

Summary of Contents for Allen-Bradley 1606-XLB90E

Page 1: ...DC Power Supply 24V 3 8 A 90 W Single phase Input Catalog Number 1606 XLB90E Reference Manual Original Instructions...

Page 2: ...y Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written per...

Page 3: ...Terminals 13 Lifetime Expectancy 13 Mean Time Between Failure 13 Electromagnetic Compatibility 14 Environment 15 Safety and Protection Features 16 Dielectric Strength 16 Approvals 17 Other Fulfilled...

Page 4: ...4 Rockwell Automation Publication 1606 RM121A EN P October 2020 Notes...

Page 5: ...compromising quality or reliability Width only 36 mm 1 42 in Efficiency up to 93 8 Low no load power losses Full power between 10 60 C 14 140 F Large screw terminals Terms Descriptions PE The abbrevia...

Page 6: ...0 158 F Input voltage AC AC 100 240V 10 Mains frequency 50 60 Hz 6 Input current AC 1 45 A 0 95 A At 120 230V AC Power factor 0 58 0 45 At 120 230V AC Input inrush current 18 A peak 40 A peak At 120 2...

Page 7: ...aker Attributes Values Notes AC 100V AC 120V AC 230V Input current Typ 1 69 A 1 45 A 0 95 A At 24V 3 8 A see Figure 3 Power factor Typ 0 6 0 58 0 45 At 24V 3 8 A see Figure 4 Start up delay Typ 50 ms...

Page 8: ...ld start Typ 14 Apeak 18 Apeak 40 Apeak At 40 C 104 F ambient cold start Max 15 Apeak 20 Apeak 43 Apeak At 25 C 77 F ambient cold start Typ 12 Apeak 16 Apeak 35 Apeak At 25 C 77 F ambient cold start I...

Page 9: ...Continuous current Output voltage 14V DC see Figure 9 Intermittent current 1 Output voltage 14V DC see Figure 9 Overload short circuit current Max 6 7 A Continuous current see Figure 9 Typ 8 6 A Inter...

Page 10: ...ring this time Attributes Values Notes AC 100V AC 120V AC 230V Hold up Time Typ 40 ms 60 ms 242 ms At 24V 1 9 A See Figure 11 Min 32 ms 48 ms 194 ms At 24V 1 9 A See Figure 11 Typ 14 ms 25 ms 119 ms A...

Page 11: ...5 A 25 at 3 8 A Power losses Typ 0 3 W 0 3 W 0 4 W At no load Typ 5 0 W 4 3 W 3 8 W At 24V 1 9 A half load Typ 9 5 W 7 9 W 6 0 W At 24V 3 8 A full load Figure 13 Efficiency Versus Output Current at 24...

Page 12: ...C OK Status Indicator Power Converter Figure 18 Front Side User Elements 1 Output terminals screw terminals Dual terminals for the negative and positive pole Both poles are internally connected Positi...

Page 13: ...hat statistically one unit fails every 100 hours if 10 000 units are installed in the field However it cannot be determined if the failed unit has been running for 50 000 hr or only for 100 hr For the...

Page 14: ...age on input EN 61000 4 5 L N 2 kV Criterion A N L PE 4 kV Criterion A Surge voltage on output EN 61000 4 5 1 kV CriterionA PE 1 kV CriterionA Conducted disturbance EN 61000 4 6 0 15 80 MHz 10V Criter...

Page 15: ...7 1 non conductive Vibration sinusoidal 1 2 17 8 Hz 1 6 mm 0 063 in 17 8 500 Hz 2 g 2 hours axis According to IEC 60068 2 6 Shock 1 30 g 6 ms 20 g 11 ms 3 bumps direction 18 bumps intotal According to...

Page 16: ...500V DC Min 500 M At delivered condition between output and PE measured with 500V DC Output overvoltage protection Typ 30 5V DC Max 32V DC If there is ananomaly inside the power supply aredundant cir...

Page 17: ...and laboratory use Part 2 201 Particular requirements for control equipment ANSI UL 61010 2 201 former UL 508 planned Listed as Open Type Device for use in Control Equipment UL Category NMTR NMTR7 E F...

Page 18: ...EN 50022 witha heightof7 5 mm 0 295 in or 15 mm 0 59 in Housing material High grade polycarbonate ABS blend material Installation clearances Keep the following min installation clearances 40 mm 1 57 i...

Page 19: ...or fuses If there is a short or an overload in one branch circuit the fuse or circuit breaker need a certain amount of overcurrent to open in a timely manner This avoids voltage loss in adjacent circ...

Page 20: ...lleled for 1 1 redundancy to gain higher system availability Redundant systems require a certain amount of extra power to support the load in case one device fails The simplest way is to put two devic...

Page 21: ...e is placed in the middle of the box and no other heat producing items are inside the box The load is placed outside the box The temperature sensor inside the box is placed in the middle of the right...