Installation
Transport System Installation
210
MagneMotion
Rockwell Automation Publication MMI-UM007F-EN-P - September 2020
3.
Insert DC-bus end-caps that on the first and last modules on the bus to cover exposed
terminals
4.
Connect the LVDC power-bus connector to the terminals on the power supply and to
the first QSHT 5700 inverter.
•
See the
Kinetix 5700 Servo Drives User Manual
for bus installa-
tion.
5.
Repeat
for each inverter in the power chain.
NOTE:
It is not necessary to connect all motors on a path to the same power supply
or to connect a power supply to only one path.
6.
Make sure that all NC LITE node controllers are mounted to grounded surfaces.
7.
Make sure that the ground stud on all NC-12 node controllers is connected to GND
(PE).
8.
Make sure that all NC-E and NC-S node controllers are grounded through the chassis
ground connection in their power connectors.
9.
Bond DC-bus power supplies, inverter modules, capacitor modules, and line filter
grounding screws by using a braided ground strap as shown in
.
10.
See
for external power connections.
Figure 5-17: QSHT 5700 Inverter Grounding
MOD
NET
2
1
1
4
I/O
QSHT 5700 Inverter
(typical)
2198-Pxxx PS
(typical)
Shared-bus Connection Systems
(DC-bus and 24V DC)
Braided Ground Strap
(typical)