Rockwell Automation Publication 440R-UM013F-EN-P - July 2021
69
Chapter 11 Troubleshooting
Figure 77 - Measure the Contact Resistance
OSSD Output Issues
If the OUT status indicator is steady green, but the output device that is
connected to terminal 14 or 24 does not energize, begin troubleshooting by
checking the voltage at the output connections. See
.
If the OUT status indicator is steady green, but the PowerFlex™ drive is
providing indication that the safety circuit is open, check the connections to
the PowerFlex drive. See
Check the PowerFlex Drive Connections on page 70
.
Check the OSSD Connections
Confirm that voltage is present at the relay terminals and the load.
shows an example of the measurement points for one output channel
(terminal 14). Since most safety circuits consist of two channels, repeat the
checking on the second channel (terminal 24).
Figure 78 - OSSD Output Connections
14
24
<1
13
OUT
23
Ohms
DMM
K1
A2
A1
K2
A2
A1
SHOCK HAZARD:
Remove the
power connections to terminal
13 before measuring the
contact resistance.
+V supply
0V
34 44 14 24
A1
A2
23
Volts
DMM
1
OUT
K1
A2
A1
K2
A2
A1
2
3
24V DC supply
24V common
Summary of Contents for 440R-D22R2
Page 12: ...12 Rockwell Automation Publication 440R UM013F EN P July 2021 Chapter 1 Overview Notes...
Page 16: ...16 Rockwell Automation Publication 440R UM013F EN P July 2021 Chapter 2 Installation Notes...
Page 81: ...Rockwell Automation Publication 440R UM013F EN P July 2021 81 Appendix A Specifications Notes...
Page 82: ...82 Rockwell Automation Publication 440R UM013F EN P July 2021 Appendix A Specifications...