The table shows indicator states if the terminal powers on and stops during startup.
Check the Display
If the terminal display is dim or unreadable:
•
check the brightness setting of the display. From Configuration mode on the terminal,
access Terminal Settings>Display Intensity.
•
check the Screen Saver settings. The backlight may be turning off or dimming the
display unexpectedly. From Configuration mode on the terminal, access Terminal
Settings>Display>Screen Saver.
Indicator States If the Terminal Stops During Startup
Fault (Red)
Indicator
Comm (Green)
Indicator
Description
Blinking
(1)
(1)
Blinking red indicates a recoverable error.
Off
Last firmware download failed.
Reload firmware using Firmware Upgrade Wizard (FUW) utility.
Blinking
EBC boot loader firmware failed or is missing.
Reload firmware using Firmware Upgrade Wizard (FUW) utility.
On
Windows CE OS firmware failed or is missing.
Reload firmware using Firmware Upgrade Wizard (FUW) utility.
On
(2)
(2)
Solid red indicates a nonrecoverable or fatal error.
Off
Fatal hardware error occurred.
Replace the logic module.
Blinking
Fatal hardware error in display.
Replace the display module.