F. Before installing the replacement 1769-SM1 module, be sure that the 

bus lever on the right-side adjacent module is in the unlocked (fully 
right) position.

G. Slide the replacement 1769-SM1 module into the open slot.

H. Connect the 1769-SM1 module and adjacent modules together by 

locking (fully left) the bus levers on the 1769-SM1 module and the 
right-side adjacent module.

I. Replace the mounting screws (or snap the module onto the DIN rail).

J. Plug the appropriate 1202-C* communications cable into its respective 

port on the 1769-SM1 module.

K. Restore 1769-SM1 module configuration using an appropriate 

configuration tool.

Step 6

Connect the module to the drive(s).

A. Plug one male end of a 1202-C* communications cable into a desired 

port (CH1, CH2 or CH3) on the 1769-SM1 module.

B. Plug the other male end of the cable into the port on the desired drive.

NOTE: For EMC regulatory compliance, there is a maximum cable 
distance limit per channel. See the “Regulatory Compliance” section in the 
1769-SM1 Compact I/O to DPI/SCANport Module User Manual for more 
information. For general cable information, see the “DPI/SCANport Cable 
Requirements/Recommendations” section in the 1769-SM1 module User 
Manual.

Step 7

Ground the module.

The 1769-SM1 module is intended to be mounted to a well-grounded 
mounting surface such as a metal panel. Additional grounding connections 
from the module’s mounting tabs or DIN rail (if used) are not required 
unless the mounting surface cannot be grounded. For additional 
information, refer to Industrial Automation Wiring and Grounding 
Guidelines
, publication No. 1770-4.1.

Summary of Contents for 1769-SM1

Page 1: ...d machine motion Causing an explosion in a hazardous environment Electrical arcing causes excessive wear to contacts on both the module and its mating connector Worn contacts may create electrical resistance ATTENTION Risk of equipment damage exists The 1769 SM1 module contains ESD Electrostatic Discharge sensitive parts that can be damaged if you do not follow ESD control procedures Static contro...

Page 2: ...ong the tongue and groove slots until the bus connectors item 3 line up with each other F Use your fingers or a small screwdriver to push the bus lever back slightly to clear the positioning tab item 4 G Move the 1769 SM1 module s bus lever fully to the left item 5 until it clicks Ensure it is locked firmly in place H Attach an end cap terminator item 6 to the last module in the system by using th...

Page 3: ...ure 1 1769 SM1 Module with MicroLogix 1500 Base Unit and Processor ATTENTION Risk of equipment damage exists During panel or DIN rail mounting of all devices be sure that all debris metal chips wire strands etc is kept from falling into the 1769 SM1 module Debris that falls into the module could cause damage on power up Compact I O Compact I O Compact I O Compact I O Compact I O End Cap or Cable C...

Page 4: ...unted modules d Drill and tap the mounting holes for the recommended M4 or 8 screw 132 mm 5 19 in 122 6 mm 4 83 in 118 mm 4 65 in 147 4 mm 5 81 in 14 7 mm 0 58 in 35 mm 1 38 in 35 mm 1 38 in 28 5 mm 1 12 in 35 mm 1 38 in 70 mm 2 76 in 35 mm 1 38 in 35 mm 1 38 in 35 mm 1 38 in 50 mm 1 97 in 40 mm 1 58 in 59 mm 2 32 in 59 mm 2 32 in Mounting Hole Dimension DIN Rail Center Line DPI SCANport MODULE CH...

Page 5: ...a flat blade screwdriver D On the right side adjacent module move its bus lever to the right unlock to disconnect it from the module being removed E Gently slide the disconnected 1769 SM1 module forward If you feel excessive resistance make sure that you disconnected the module from the bus and that you removed both mounting screws or opened the DIN latches ATTENTION Risk of equipment damage exist...

Page 6: ...2 C communications cable into a desired port CH1 CH2 or CH3 on the 1769 SM1 module B Plug the other male end of the cable into the port on the desired drive NOTE For EMC regulatory compliance there is a maximum cable distance limit per channel See the Regulatory Compliance section in the 1769 SM1 Compact I O to DPI SCANport Module User Manual for more information For general cable information see ...

Page 7: ...r an initialization If the status indicators go red there is a problem Refer to the Troubleshooting chapter in the 1769 SM1 Compact I O to DPI SCANport Module User Manual Step 9 Read the 1769 SM1 Compact I O to DPI SCANport Module User Manual for information to configure and determine how to apply the network to the host product s ATTENTION Risk of equipment damage injury or death exists Unpredict...

Page 8: ...x 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Power Control and Information Solutions Headquarters U S Allen Bradley Drives Technical Support Tel 1 262 512 8176 Fax 1 262 512 2222 Email support drives ra rockwell com Online www ab com support abdrives Publication 1769 IN083A EN P May 2012 P N 148231 Cop...

Reviews: