Replacement Parts
MicroLogix 1400
Replacement Kits
The table below provides a list of replacement parts and their catalog number.
Lithium Battery (1747-BA)
Installation
Follow the procedure below to ensure proper replaceable battery installation.
1. Insert a battery into the battery pocket with wires facing up.
2. Insert the battery wire connector into the battery connector.
3. Secure the battery connector wires around the 1762 expansion bus
connector as shown in
.
Topic
Page
MicroLogix 1400 Replacement Kits
Description
Catalog Number
Lithium Battery
1747-BA
IMPORTANT
When the controller’s Battery Low indicator is lit, check whether the battery
wire connector is connected correctly or replace the replaceable battery
with a new one immediately. When the indicator turns on, it means that
either the battery is disconnected, or that the battery requires
replacement. The controller is designed to operate for up to 2 weeks, from
the time that the indicator first turns on. We recommend that you replace
the battery immediately when the indicator turns on.