Heating engineer
Installation, use and maintenance manual – Supercromo
13
3
Figure 3.3
Installation with coaxial pipes with 90° outlet
A Air pipe Ø 49 mm
B
Flue gas pipe Ø 35 mm
C
Adhesive gasket
D Support bracket
E
Wall terminal Ø 35 mm
F
90° casing for coaxial exhaust
A
B
C
D
E
F
IM14045
Figure 3.4
Installation with wall separate ducts
A Air/flue gas pipe Ø 35 mm
B
Elbow 90° M/F Ø 35 mm
C
Adhesive gasket
D Support bracket
E
Wall terminal Ø 35 mm
F
90° casing for separate exhaust
G Condensate discharge Ø 35 mm
D
A
B
A
A
A
A
A
B
B
B
E
F
C
G
For further information on the installation of the
flue gas exhaust/air intake duct, please refer to the
installation guide for the flue gas exhaust/air intake
ducts D-GPP001, available on the Robur website.
3.4.2.1
Installation with separate ducts
If the appliance is installed with separate pipes, suitable
pipes and components, available as optional, must be
used.
At the design stage, it must be verified that the sum of the
pressure drop of all components used does not exceed
the value of the available residual head (Table 3.2
p. 13).
Table 3.2
Separate exhaust pressure drop table
Description
Code
3001
3002
residual head
Pa
25
25
Air pipe internal Ø 33 mm
OPRL000
Pa/m
0,6
0,6
Horizontal flue gas pipe internal Ø 33 mm
OPRL000
Pa/m
1,5
1,5
Vertical flue gas pipe internal Ø 33 mm
OPRL000
Pa/m
0,2
0,2
90° elbow on air pipe
OCRV000
Pa
0,6
0,6
90° elbow on flue gas pipe
OCRV000
Pa
1,0
1,0
Casing complete with internal elbow for flue gas exhaust
OCFF002
Pa
1,5
1,5
Casing without internal elbow for flue gas exhaust
OCFF002
Pa
1,0
1,0
Roof terminal Ø 35 mm
OTRM002
Pa
0,0
0,0
Wall terminal
JTRM000B
Pa
0,0
0,0
Condensate discharge Ø 35 mm
OSCR003
Pa
0,0
0,0
If the flue gas pipe is longer than 1,5 metres, a condensate drain (available as OSCR003 optional) must be installed