First start-up
Installation, use and maintenance manual – Gitié ARAY
35
5
5.2
ELECTRONIC ADJUSTMENT ON THE
MACHINE - MENUS AND PARAMETERS
OF THE S61 BOARD AND OF THE AY10
BOARD
Firmware
The instructions on the use of the S61 electronic board
concern the firmware version 3.035.
The instructions on the use of the AY10 electronic board
concern the firmware version 3.108.
Figure 5.1
S61 electronic board on GAHP/GA unit
A
4 digit display
B
Knob
C
CAN port
Figure 5.2
AY00-120 unit electronic board (AY10+S70)
A
4 digit display
B
Knob
C
CAN port
Display
The 4-digit displays of the boards (Detail A in Figure 5.1
and in Figure 5.2
p. 35) are as follows:
▶
The first digit (on the left, green) indicates the menu num-
ber (e.g. "0.", "1.", "2.", ... "8.").
▶
The last three digits (on the right, red) indicate a code or a
value for a parameter, among those included in the selected
menu (e.g. "__6" "_20", "161").
(e.g. menu+parameter "1.__6", "2._20", "3.161").
Knob
One of the following actions may be done with the board knob
(Detail B in Figure 5.1
p. 35 and in Figure 5.2 p. 35):
▶
Enter the menu list (by pressing the first time).
▶
Scroll the menu list, or a series of parameters in a menu (by
turning).
▶
Select a menu or a parameter (by pressing).
▶
Modify and confirm the setting of a parameter (turning and
pressing).
▶
Execute a command (by pressing).
▶
Exit a menu and go back to the higher level by selecting the
letter “E” which is displayed at the end of the menu list or of
a series of parameters in a menu.
The letter "E" is displayed at the end of the menu list or of a series
of parameters in a menu, and indicates the exit to go back to the
higher level by pressing the knob.
Menus and Parameters
The menus may be display only (functional data or parameters),
display and setting (parameters) or control (reset).
Menu for the user (but for the installer and TAC as well)
▶
The menu "0.", display only, for functional data detected in
real time.
▶
The menu "1.", display only, for current values of appliance
parameters.
▶
Menu "2.", control, to execute flame control unit reset opera-
tions, reset errors (Paragraph 7.5
p. 39).
▶
Menu "3.", display and setting, to set the value of some sys-
tem parameters (e.g. water set point temperature); the val-
ues are initialised by the TAC at first start-up.
It is accessed without password.
Menu for the installer or TAC (not accessible to the user)
▶
Menu "4.", "5.", "6." and "9." are password-protected. These are
specific sections, exclusively intended for qualified person-
nel (installer or TAC). For information see the Service manual.
▶
Menu "7." is display only and intended for the manufacturer.
▶
Menu "8." is empty, it may be selected but not used.
Special key for the knob
To access the menus and parameters of the boards, use
the special standard supplied key, fastened on the gas
pipe above the electrical panel. The key allows the knob
to be operated through the suitable hole in the electri-
cal panel cover, operating safely away from live compo-
nents.
Always keep the key for future uses.
How to access the menus and parameters
Before Starting:
(1) Power supply switch on.
(2) Display of the board showing in sequence the detect-
ed water temperature data (if the appliance is in normal
operation), or the flashing malfunction and failure codes
(if the appliance is in failure).
To access the menus and parameters of the board, pro-
ceed as follows (see also Figure 5.1
p. 35 and Figure
5.2
1. Remove the front panel by removing the fixing screws.
2. Remove the cover of the electrical panel to access the
board knob.
3. Act on the knob by means of the special key through the
suitable hole.
4. Press the knob once to display the menus: the first menu
is displayed, "0." (= menu 0).