Heating engineer
Installation, use and maintenance manual – Next-G
29
3
supply pressure of 50 mbar.
The appliance's gas supply pressure, both static and dy-
namic, must comply with Table 3.1
p. 29, with tolerance
± 15%.
Non compliant gas pressure (Table 3.1
may damage the appliance and be hazardous.
The Next-G gas unit heaters are also approved for
use with I20 gas, i.e. a gas mix with a 20% maxi-
mum of hydrogen.
Table 3.1
Network gas pressure
Gas supply pressure [mbar]
Product
category
Country of destination
G20
G25
G25.1
G25.3
G2.350
(1)
G27
G30
G31
II
2H3B/P
AL, BG, CH, CY, CZ, DK, EE, FI, GR, HR, IT, LT, LV, MK, NO,
RO, SE, SI, SK, TR
20
30
30
AT, CH
20
50
50
II
2H3P
AL, BG, CH, CZ, ES, GB, GR, HR, IE, IT, LT, LV, MK, PT, SI,
SK, TR
20
37
RO
20
30
AT
20
50
II
2ELL3B/P
DE
20
20
50
50
II
2Esi3P
FR
20
25
37
II
2Er3P
20
25
37
II
2H3B/P
HU
25
30
30
II
2HS3B/P
25
25
30
30
II
2E3P
LU
20
50
II
2L3B/P
NL
25
30
30
II
2L3P
25
37
II
2EK3B/P
20
25
30
30
II
2EK3P
20
25
30
II
2E3B/P
PL
20
37
37
I
2E
20
II
2ELwLs3B/P
20
13
20
37
37
II
2ELwLs3P
20
13
20
37
I
2E(R)
BE
20
25
I
2E(S)
20
25
I
3P
37
I
3P
IS
30
I
2H
LV
20
I
3B/P
MT
30
30
I
3B
30
1
The G 75 EC, G 90 and G 90 EC gas unit heaters cannot be operated with this type of gas.
The appliance gas supply pressure, both static and dynamic, must comply with the values in the Table, with a tolerance of ± 15%.
3.2.5
Vertical pipes and condensate
▶
If needed, vertical gas pipes must be fitted with siphon
and discharge of the condensate that may form inside
the pipe.
▶
If needed, insulate the piping.
3.2.6
LPG pressure reducers
With LPG the following must be installed:
▶
A first stage pressure reducer, close to the liquid gas
tank.
▶
A second stage pressure reducer, close to the appli-
ance.
3.3
COMBUSTION PRODUCTS EXHAUST
Compliance with standards
The appliance is approved for connection to a
combustion products exhaust duct for the types
shown in Table 1.2
3.3.1
Flue gas exhaust connection
▶
Ø 80 mm with gasket, on the rear, at the top (see di-
mensional diagrams, Paragraph 1.2
For all models, it is possible to move the fumes gas outlet
connection from the rear position to the top of the unit.
How to move the fumes gas outlet
1. Remove the gas unit heater top panel.
2. Remove the blind cover of the upper flue gas
exhaust (detail 7 in the dimensional diagrams,
Paragraph 1.2
p. 8) from the top panel.
3. Unscrew the three screws fixing the flue gas ex-
haust to the rear collar.