Maintenance
Installation, use and maintenance manual – Caldaria Con export
49
7
of 30 °C to a maximum of 80 °C.
6.3.6
Setting the DHW temperature
The temperature is adjusted using the
and
keys of the
DHW circuit
(Figure 6.1
p. 47):
1. Pressing the
key decreases the temperature.
2. Pressing the
key increases the temperature.
3. The temperature adjustment field of the domestic hot water
ranges from a minimum of 35 °C to a maximum of 60 °C.
6.3.7
OFF mode
In this operating mode the boiler no longer provides heating
and DHW, but the antifreeze and pump anti-lock systems remain
active.
To switch the boiler to the OFF operating mode, press the
key; the fixed
symbol will appear on the display, indi-
cating that the function has been activated.
If the boiler was previously in operation, it is switched off and
the post-ventilation and post-circulation functions are activated.
If you decide to shut down the boiler for a long period of time,
secure it by operating in one of the following two ways:
1. Call the TAC that will empty the water system, where there
is no provision for the use of antifreeze, and disconnect the
power supply, water and gas.
2. Leave the boiler in the OFF operating mode, keeping the
power and gas supply active, so that the antifreeze function
and the pump anti-lock function can be activated.
6.3.8
Pump antifreeze and anti-lock function
Refer to Paragraph 3.5
6.4
REMOTE CONTROL OPERATION
(OPTIONAL)
For switching on, adjusting and switching off the boiler,
refer to the instructions supplied with the remote
control.
INFO MENU DISPLAY
To view the boiler data from Info menu you have to:
1. Press the
key (Figure 6.1
p. 47). The info code will be
displayed on the left side of the screen and its value will be
displayed on the centre of the screen.
2. To scroll through the list of displayable data, use the
and
keys of the heating side
.
3. Press the
key to exit the Info menu.
Table 6.1
p. 49 shows the list of data that can be viewed from
the Info menu for Caldaria 35 and Caldaria 55.1, Table 6.2
those for Caldaria 100.2.
Table 6.1
List of displayable data from menu Info
Info code
Description
d0
Not used temperature
d1
Outdoor probe temperature
d2
Combustion blower speed
d3
Not used temperature
d4
Return probe temperature
d5 - dE
Not-operating data
Table 6.2
Caldaia 100.2 - List of displayable data from menu Info
Info code
Description
d00
Not used temperature
d01
Outdoor probe temperature
d02
Not used temperature
d03
Percentage of total power delivered by the boiler
d10
Delivery probe temperature of the master unit
d11
Return probe temperature of the master unit
d12
Blower speed of the master unit
d20
Delivery probe temperature of the slave unit
d21
Return probe temperature of the slave unit
d22
Blower speed of the slave unit
7
MAINTENANCE
Correct maintenance prevents problems, assures effi-
ciency and keeps running costs low.
Maintenance operations described herein may exclu-
sively be performed by the TAC or skilled maintenance
technician.
Any operation on internal components may exclusively
be performed by the TAC.
Before performing any operation, switch off the appli-
ance by means of the control device and wait for the end
of the shutdown cycle, then disconnect power and gas
supply, by acting on the electrical disconnector and gas
valve.
It is recommended that the following operations and checks be
carried out each year:
▶
Combustion circuit functionality and heat exchange control:
Burner and flue exhaust duct inspection
Cleaning of burner and water/flue exchanger (if applica-
ble)
Flame ignition/detection system control
▶
Hydraulic circuit and internal components functionality
check:
Hydraulic circuit control (pipes, gaskets)
Expansion tank
Control and safety devices
Water temperature probe
▶
Periodic analysis of combustion, in accordance with regula-
tions in force
7.1
HYDRAULIC BOILER EMPTYING
Whenever there is a need to empty the boiler, proceed as follows:
▶
Switch off the boiler by pressing the
button.
▶
Switch off the power supply via the main switch.
▶
Wait until the boiler has cooled down.
▶
Connect a hose emptying point and connect the other end
of the hose to a suitable drain.
▶
Open the drain tap (Figure 7.1
p. 50 for Caldaria 35,
Figure 7.2
p. 50 for Caldaria 55.1 and Figure 7.3 p. 50 for
Caldaria 100.2).