![Robur B15 Generators Series Installation, User And Maintenance Manual Download Page 23](http://html1.mh-extra.com/html/robur/b15-generators-series/b15-generators-series_installation-user-and-maintenance-manual_1471526023.webp)
Installation, user and maintenance manual
– Series B15 Generators
23
table 3�5
offsets
offset
[mbar]
[Pa]
nominal
0,1
10
Offsets.
Check that the CO
1.
2
percentage is as given in 3.1
→
17. If it is not, adjust the offset
again until the CO
2
percentage is as given in 3.1
→
17.
Turn the appliance off and back on again two or three times to check that the new
2.
setting is stable.
Disconnect the pressure gauge and screw pressure fitting "B" seal screw back in
3.
again.
Restore the appliance, making sure to fit the cap onto screw "A".
4.
figure 3�10
Gas Valve.
LeGend
A
offset adjuster screw
B
outlet gas pressure fitting
C
inlet gas pressure fitting
A
B
C
Summary of Contents for B15 Generators Series
Page 4: ...4...
Page 6: ...6...
Page 12: ...12...
Page 24: ...24 3 6 WIRING DIAGRAMS Figure 3 11 Installation diagram LEGEND vedi disegno...