2
VFD (inverter)
DANGER
•
Electric shock hazard!
High voltage inside electric panel. DO NOT touch bare
terminals and/or wires.
Figure 2: VFD control panel
NOTE 1:
VFD setup must be performed only when the
drive is stopped.
NOTE 2:
After setting parameter 02.00 to 9, VFD
displays End , and gets back to the main indication
mode. After this, continue setup process from parameter
00.03.
Parameters changing procedure
1. Locate the VFD control panel, see Fig 2.
2. To change or view parameter value, press
, the display shows 00.__
3. Press
or
to choose the first two digits of the parameter (for example, 02).
4. Press
again, display shows 02.00 .
5. Press
or
to choose the second two digits of the parameter, for example, 02.11 .
6. Press
again to see the current value of the parameter. Change value, if needed, with
or
.
7. Press
to confirm and save the new value, the display shows End .
8. Press
to return back to the previous level of selection or to the main mode.
Parameter
Value
Description
00.02
9 Settings initialization
00.03
0 Start-up display selection
01.00
70.00 Maximum output frequency
01.16
4 Auto accel/decel
02.00
3 Source of first master frequency command: RS-485
02.01
4 Source of first operation command: RS-485
02.04
0 Motor direction control
02.07
1 Up/Down mode
02.09
0 Source of second frequency command
02.10
1 1st and 2nd master frequency command combination
02.11
40.0 Keypad frequency command
09.00
5 VFD communication address
09.01
1 Transmission speed: 9600 bps
09.02
3 Transmission fault treatment:keep operating
09.04
1 Communication protocol: ASCII 7, E, 1
Technical service manual 2692
4