13
SPECIFICATION
Ambient Temperature:
23±5°C
Ambient Humidity:
45 - 75%RH
Error Limit:
±(% R dgt Count)
Loop Impedance:
Range
Display Range
Rated Test Current
and Time
Accuracy
20
Ω
0.00 - 19.99
Ω
25A/10ms
±(3%rdg+4LSD)
200
Ω
0.0 - 199.9
Ω
2.3A/20ms
2000
Ω
0 - 1999
Ω
15mA/360ms
20
Ω
NO TRIP
0.00 - 19.99
Ω
L-N<20
Ω
*
1
P-N: 25A/30ms
N-E: 15mA/approx. 2s
±(3%rdg+6LSD)
20
Ω
NO TRIP
0.00 - 199.9
Ω
L-N<20
Ω
*
1
*1: If the impedance between L-N is 20
Ω
or more, “no” is displayed on the
display and no measurement can be made. In this case, disables NO TRIP
function and make measurement.
Prospective Short-Circuit Current:
Range
Display Range
Rated Test Current
and Time
Accuracy
200A
0.00 - 199.9A
2.3A/20ms
±(3%rdg+4LSD)
2000A
0.0 - 1999A
25A/10ms
20kA
0.00 - 19.9kA
25A/10ms
200A
NO TRIP
0.00 - 199.9A
L-N<20
Ω
*
1
P-N: 25A/30ms
N-E: 15mA/approx. 2s
±(3%rdg+6LSD)
2000A
NO TRIP
0.00 - 1999A
L-N<20
Ω
*
1
20kA
NO TRIP
0.0 - 19.9kA
L-N<20
Ω
*
1
*1: If the impedance between L-N is 20
Ω
or more, “no” is displayed on the
display and no measurement can be made. In this case, disables NO TRIP
function and make measurement.