TYPICAL ROBERTSHAW HOT SURFACE APPLICATION

PILOT TUBING

NOTE:

 Some hot surface applications use the pilot outlet, if so proceed 

as directed below. If not used install pilot outlet tubing plug packaged 
in the 720-079 gas valve kit then proceed to “wiring”.
1. Make sure tubing is free of burrs and dirt.
2.  We strongly recommend that the pilot orifice be checked and 

cleaned if necessary at this time.

3.  Connect pilot tubing into the control using fitting provided, and 

tighten for a gas-tight seal.

WIRING

DO NOT

 short gas valve terminals. This will damage wall thermostat 

and void warranty.

1.  Check the system for the proper transformer by comparing the VA 

ratings of the transformer and the system. The system rating is deter

-

mined by 

multiplying the voltage draw times the amp draw. 

INSTALLATION INSTRUCTIONS – HOT SURFACE APPLICATIONS

Normally 20VA transformers are sufficient for heating only applica tions 
and 40VA for heating /cooling applications.

NOTE:

 Improper transformer VA rating will cause erratic system 

 

operation.
2.  Locate the white wire terminal adaptor (jumper) that is included 

with the 720-079 gas valve.

3.  Connect the white wire terminal adaptor to the “M” and “P” termi

-

nals on the 720-079 gas valve.

4.  Determine which wire was connected to the “main valve” terminal 

on the original valve. Connect this wire to the remaining terminal on 
the white wire terminal adaptor.

Summary of Contents for Uni-Kit 720-079

Page 1: ...Temperature 40 to 175 F Maximum Inlet Pressure 7 W C natural gas 14 W C L P gas REGULATION CAPACITIES SIZE TYPE GAS NATURAL L P MIN MAX MIN MAX 3 8 x 3 8 15 000 175 000 15 000 280 000 1 2 x 3 8 15 000 175 000 15 000 280 000 1 2 x 1 2 15 000 200 000 15 000 320 000 1 2 x 3 4 15 000 200 000 15 000 320 000 3 4 x 3 4 15 000 200 000 15 000 320 000 INTERMITTENT PILOT HOT SURFACE DIRECT SPARK PIPING 1 Che...

Page 2: ...gging of the tubing and improper regula tor operation If bleed tubing is not used the regulator vent must be properly shielded from moisture LEAK TEST Leak test with a soap solution after installing with main burner on Coat pipe and tubing joints gasket etc with soap solution Bubbles indicate leaks PILOT TUBING 1 Make sure tubing is free of burrs and dirt 2 We strongly recommend that the pilot ori...

Page 3: ... 1 Check the system for the proper transformer by comparing the VA ratings of the transformer and the system The system rating is deter mined by multiplying the voltage draw times the amp draw INSTALLATION INSTRUCTIONS HOT SURFACE APPLICATIONS Normally 20VA transformers are sufficient for heating only applica tions and 40VA for heating cooling applications NOTE Improper transformer VA rating will ...

Page 4: ...nt for heating only applica tions and 40VA for heating cooling applications NOTE Improper transformer VA rating will cause erratic system operation 2 Locate the white wire terminal adaptor jumper that is included with the 720 079 gas valve 3 Connect the white wire terminal adaptor to the M and P termi nals on the 720 079 gas valve 4 Determine which wire was connected to the main valve terminal on ...

Page 5: ...ifications 4 Replace regulator adjustment screw cap A REGULATOR CONVERSION CAUTION Main burner and pilot orifices must be changed when regu lator is converted from one type of gas to another 1 Turn off gas and electricity to appliance 2 Remove slotted cap A adjusting screw B and natural gas spring not color coded C from control 3 Install new L P spring color coded with a black strip 4 Install new ...

Page 6: ...gon and Uni Line are trademarks of Robertshaw its subsidiaries and or affiliated companies All other brands mentioned may be the trademarks of their respective owners For Technical Service Telephone 1 800 445 8299 Facsimile 1 630 260 7294 TechnicalService robertshaw com www uni line com www robertshaw com 2014 Robertshaw 07 14 1 870 RevC 6 ...

Reviews: