background image

INSTALLATION DATA

720-079 UNIVERSAL ELECTRONIC  

IGNITION GAS VALVE UNI-KIT

®

The Robertshaw® 720-079 Universal Electronic Ignition Gas Valve 

 

Uni-Kit® is de signed to work equally well on Intermittent Pilot, Direct 
spark and Hot Surface applications.
The 720-079 features a manual selector, wiring connections and ad-
justments that are all easily accessible on the top of the valve. The 
720-079 Uni-Kit has a pressure regulator that is pre-set at 3.5” W.C. 
for natural gas. For L.P. gas applications the valve can be converted by 
using a pressure regulator conversion kit that is included.
The 720-079 incorporates a manual valve, pilot valve (dual automatic 

valves and a main gas pressure regulator all in a small compact valve 

with a swing radius of 3-9/16’’. The small size of the 720-079 lends 
itself to replacing many O.E.M. and competitive valves. The 720-079 
is multi-positional and can be mounted in any position, except upside 
down.

APPLICATION LIMITATIONS

Do not use on direct spark or hot surface applications if original valve 
was a “slow opening” type. Also 720-079 will not replace Robertshaw 
7000K series or White-Rodgers “cycle pilot” gas valves.

SPECIFICATIONS

Electrical Ratings 

24 VAC, .45 amps

 

Pressure Regulator

 

  Natural Gas 

factory set at 3.5” W.C.

 

  L.P. gas 

factory set at 11.0” W.C.

 

Ambient Temperature 

-40° to 175°F

 

Maximum Inlet Pressure 

7” W.C. - natural gas

 

 

14” W.C. - L.P. gas

REGULATION CAPACITIES

SIZE

TYPE GAS

NATURAL

L.P.

MIN.

MAX.

MIN.

MAX.

3/8” x 3/8"

15,000

175,000

15,000

280,000

1/2” x 3/8”

15,000

175,000

15,000

280,000

1/2" x 1/2"

15,000

200,000

15,000

320,000

1/2" x 3/4"

15,000

200,000

15,000

320,000

3/4" x 3/4"

15,000

200,000

15,000

320,000

INTERMITTENT PILOT  •  HOT SURFACE  •  DIRECT SPARK

PIPING

1.  Check replacement valve for multiple outlets (side outlets). If it has 

them, be sure all unused outlets are plugged using the socket plugs 
provided.

2.  Pipe or tubing must be clean and free of scale and dirt.
3.  Make sure gas piping is pressure tested before control is connected. 

High pressure can damage control causing a hazardous condition. Do 
not subject control to more than 1/2 PSI, (14” W.C.) inlet pressure.

CAUTION

THIS DEVICE SHOULD BE INSTALLED BY A QUALIFIED 

 

TECH NICIAN WITH DUE REGARD FOR SAFETY AS IMPROPER 

 

IN STALLATION COULD RESULT IN A HAZARDOUS CONDITION.

4.  If it’s not already installed, a drip leg (sediment trap) must be added to 

the gas supply line to the control. (See figure below.) All piping must 

comply with local 

codes and ordinances and with National Fuel Gas Code 

(ANSI Z223.1/ NFPA, No. 54).

INSTALLATION INSTRUCTIONS - ALL APPLICATIONS 
Turn off gas supply and electrical power to equipment before servicing.

NOTE:

To prevent unsafe attempts at repair, special screws are used and replacement 

parts are NOT

 available.

* A plug is included for hot surface and direct spark applications.

1

Summary of Contents for Uni-Kit 720-079

Page 1: ...Temperature 40 to 175 F Maximum Inlet Pressure 7 W C natural gas 14 W C L P gas REGULATION CAPACITIES SIZE TYPE GAS NATURAL L P MIN MAX MIN MAX 3 8 x 3 8 15 000 175 000 15 000 280 000 1 2 x 3 8 15 000 175 000 15 000 280 000 1 2 x 1 2 15 000 200 000 15 000 320 000 1 2 x 3 4 15 000 200 000 15 000 320 000 3 4 x 3 4 15 000 200 000 15 000 320 000 INTERMITTENT PILOT HOT SURFACE DIRECT SPARK PIPING 1 Che...

Page 2: ...gging of the tubing and improper regula tor operation If bleed tubing is not used the regulator vent must be properly shielded from moisture LEAK TEST Leak test with a soap solution after installing with main burner on Coat pipe and tubing joints gasket etc with soap solution Bubbles indicate leaks PILOT TUBING 1 Make sure tubing is free of burrs and dirt 2 We strongly recommend that the pilot ori...

Page 3: ... 1 Check the system for the proper transformer by comparing the VA ratings of the transformer and the system The system rating is deter mined by multiplying the voltage draw times the amp draw INSTALLATION INSTRUCTIONS HOT SURFACE APPLICATIONS Normally 20VA transformers are sufficient for heating only applica tions and 40VA for heating cooling applications NOTE Improper transformer VA rating will ...

Page 4: ...nt for heating only applica tions and 40VA for heating cooling applications NOTE Improper transformer VA rating will cause erratic system operation 2 Locate the white wire terminal adaptor jumper that is included with the 720 079 gas valve 3 Connect the white wire terminal adaptor to the M and P termi nals on the 720 079 gas valve 4 Determine which wire was connected to the main valve terminal on ...

Page 5: ...ifications 4 Replace regulator adjustment screw cap A REGULATOR CONVERSION CAUTION Main burner and pilot orifices must be changed when regu lator is converted from one type of gas to another 1 Turn off gas and electricity to appliance 2 Remove slotted cap A adjusting screw B and natural gas spring not color coded C from control 3 Install new L P spring color coded with a black strip 4 Install new ...

Page 6: ...gon and Uni Line are trademarks of Robertshaw its subsidiaries and or affiliated companies All other brands mentioned may be the trademarks of their respective owners For Technical Service Telephone 1 800 445 8299 Facsimile 1 630 260 7294 TechnicalService robertshaw com www uni line com www robertshaw com 2014 Robertshaw 07 14 1 870 RevC 6 ...