Figure 5: Dimensions (Inches)

CONTROL MOUNTING

Mount the ETC to a wall or any flat surface using a combination of any 

two or more of the slotted holes located on the back of the control 

case. The control’s components are not position sensitive, but should 

be mounted so that they can be easily wired and adjusted. Avoid  

excessive conditions of moisture, dirt, dust and corrosive atmosphere.

The ETC has provisions for 1/2 inch conduit connections. The conduit 

hub should be secured to the conduit before securing the hub to the 

plastic housing of the control. When using the conduit entry in the rear 

of the case, a standard plug should be inserted into the conduit hole 

in the bottom. Caution should be 

exercised not to damage the control 

circuit board or wiring when installing 

a conduit connector.

CAUTION

Read all of the information in these instructions before installing 

or operating the ETC control.
The schematic drawings and other information included in these 

installation  instructions  are  for  the  purpose  of  illustration  and 

general reference only.
ETC controls are not to be located in areas of significant moisture, 

dirt or dust as use of the control in such environment may cause 

personal injury or property damage and is likely to shorten the 

control life.
It  is  the  responsibility  of  the  installer  and  the  user  to  assure 

that the application and use of the ETC control is in compliance 

with all applicable federal, state, and local laws, regulations and 

ordinances,  including,  without  any  limitation,  all  requirements 

imposed  under  the  National  Electric  Code  and  any  applicable 

building codes.

PRÉCAUTIONS 

Lire toutes les informations contenues dans ces instructions avant 

d’installer ou d’utiliser le contrôleur ETC.
Les schémas et toutes les autres informations figurant dans ces 

instructions d’installation sont indiqués à des fins d’illustration et 

de référence générale seulement.
Les  contrôleurs  ETC  ne  doivent  pas  être  placés  dans  des  zones 

ayant un taux d’humidité élevé, de la saleté ou de la poussière, 

car l’utilisation du contrôleur dans de tels environnements peut 

engendrer des blessures ou des dommages matériels et est 

susceptible de raccourcir la durée de vie du contrôleur.
Il  est  de  la  responsabilité  de  l’installateur  et  de  l’utilisateur  de 

s’assurer que l’installation et l’utilisation du contrôleur ETC soit 

faites en conformité avec tous les règlements, lois, et ordonnances 

fédéraux,  provinciaux,  et  locaux,  y  compris,  sans  y  être  limité, 

toutes les exigences imposées par la National Electric Code ainsi 

que tous les codes du bâtiment, en vigueur.

Summary of Contents for RANCO ETC Series

Page 1: ... 25 in diameter with 8 ft cable IP67 rated Power Consumption 120 208 240V AC 100 milliamps 24V AC 2 6V AC 1 Relay Electrical Ratings 120V 208 240V NO Contact Full load amps 9 8 A 4 9 A Locked rotor amps 58 8 A 29 4 A Resistive amps 9 8 A 4 9 A Horsepower 1 2 hp 1 2 hp NC Contact Full load amps 5 8 A 2 9 A Locked rotor amps 34 8 A 17 4 A Resistive amps 5 8 A 2 9 A Horsepower 1 4 hp 1 4 hp Pilot Dut...

Page 2: ...e 2 Step 5 Press the SET key again to access the stage 2 setpoint The LCD will display the current setpoint and the S2 annunciator will be blinking on and off to indicate that the control is in the setpoint mode Then press either the up Ç key to increase or the down È key to decrease the setpoint to the desired temperature Step 6 Press the SET key again to access the stage 2 differential The LCD w...

Page 3: ... Stage 1 Cooling or Heating Mode 5 S2 blinking Stage 2 Setpoint Temperature 6 DIF 2 blinking Stage 2 Differential Temperature 7 C2 H2 Stage 2 Cooling or Heating Mode Figure 4 Lockout Switch INSTRUCTIONS CONCERNANT L INSTALLATION AVERTISSEMENT Risque de choc électrique Couper le courant à la source d alimentation principale avant d installer le contrôleur ETC NE PAS rétablir l alimentation élec tri...

Page 4: ...use personal injury or property damage and is likely to shorten the control life It is the responsibility of the installer and the user to assure that the application and use of the ETC control is in compliance with all applicable federal state and local laws regulations and ordinances including without any limitation all requirements imposed under the National Electric Code and any applicable bui...

Page 5: ... representation of the sensor temperature with 0 volts 30 F and 10 volts 220 F See figure 8 for wiring information and Figure 5 for location of the entry hole The reference for this output is designated by the symbol on the wiring diagram The output signal is designated by the symbol Figure 8 0 10 V Analog Output Located on Power Lower Circuit Board Figure 7 Typical Wiring Diagram for 24 VAC Power...

Page 6: ...dicates a problem check sensor resistance to determine if sensor or control is at fault 4 To check sensor resistance disconnect sensor and measure the resistance across the leads while measuring temperature at the sensor SENSOR REPLACEMENT Figure 9 Sensor replacement on Display Upper Circuit Board Sensor Replacement ETC models are available with Quick Connect Sensor feature that allows for easy se...