![Roberts Gorden UltraVac URVBNC Installation Manual Download Page 16](http://html.mh-extra.com/html/roberts-gorden/ultravac-urvbnc/ultravac-urvbnc_installation-manual_1469605016.webp)
ROBERTS GORDON
®
ULTRAVAC™ C
ONTROLLER
I
NSTALLATION
M
ANUAL
12 of 65
SECTION 2: SPECIFICATIONS
2.1 ROBERTS GORDON
®
ULTRAVAC™ Controller
2.1.1 Standard Enclosure
Construction: 16 gauge painted steel, hinged
door, removable knockouts
provided.
Dimensions: W x H x D
(in): 14.7 x 17.7 x 3.5
(cm): 37.3 x 45.0 x 8.9
2.1.2 Electrical
Power Supply: 120 V (+/- 10%) 1 Ø, 60 Hz
UL Standard: UL 916 / C22.2 No. 205-M1983
Universal Inputs:
Eight Universal Inputs
Thermistor
0-10 Vdc
4-20m A
Resistance
Dry contact
Analog Output:
One Analog Output 0-10 Vdc
Digital Inputs:
Digital Inputs: Timed, dry contact
Digital Outputs:
Four Digital Output: Single Pole 3 A 120 Vac
Volt Free Contacts:
Three Digital Output: Single Pole
Ports:
RS-485 Communications Bus
RS-232 Direct Connect Bus
RS-232 Modem Socket
2.2 ROBERTS GORDON
®
ULTRAVAC™ Unitary
Controller
2.2.1 Standard Enclosure
Construction: 16 gauge painted steel, hinged
door, removable knockouts
provided.
Dimensions: W x H x D
(in): 14.7 x 17.7 x 3.5
(cm): 37.3 x 45.0 x 8.9
2.2.2 Electrical
Power Supply: 120 V (+/- 10%) 1 Ø, 60 Hz
UL Standard: UL 916 / C22.2 No. 205-M1983
Universal Inputs:
Eight Universal Inputs
Thermistor
0-10 Vdc
4-20m A
Resistance
Dry contact
Analog Output:
One Analog Output 0-10 Vdc
Digital Inputs:
Digital Inputs: Timed, dry contact
Digital Outputs:
Three Relay Outputs: Normally Open Single Pole
Rating: 8 A 120 VAC
Ports:
RS-485 Communications Bus
RS-232 Direct Connect Bus
RS-232 Modem Socket
2.3 ULTRAVAC™ BMS Link Controller
2.3.1 Standard Enclosure
Construction: 16 gauge painted steel, hinged
door, removable knockouts provided.
Dimensions:
W x H x D
(in):14.7 x 17.7 x 3.5
(cm): 37.3 x 45.0 x 8.9
2.3.2 Electrical
Power Supply: 120V (+/-10%) 1 Ø, 60 Hz
Ports:
RS-485 Communications Bus
Ethernet/IP
2.4 NEMA 4 Enclosure (P/N 10080302)
Description:
NEMA 4 enclosure is sold separately
as an option, for ULTRAVAC™
Controller and ULTRAVAC™ BMS
Link Controller.
Standard enclosures are field
mounted inside the NEMA 4
enclosure.
Construction: 14 gauge painted steel, hinged door
with 19" (48.3 cm) x (40.6 cm) 16"
window.
Dimensions:
W x H x D
(in): 24 x 24 x 9
(cm): 61.0 x 61.0 x 22.9
Protection
Rating:
NEMA 4, 12
2.5 Repeater
2.5.1 Standard Enclosure
Summary of Contents for UltraVac URVBNC
Page 2: ......
Page 4: ......
Page 7: ...SECTION 1 INTRODUCTION 3 of 65 FIGURE 1 Connected Components ...
Page 8: ...ROBERTS GORDON ULTRAVAC CONTROLLER INSTALLATION MANUAL 4 of 65 Connected Components continued ...
Page 48: ...ROBERTS GORDON ULTRAVAC CONTROLLER INSTALLATION MANUAL 44 of 65 FIGURE 25 End Vent Vacuum ...
Page 53: ...SECTION 9 TROUBLESHOOTING 49 of 65 Troubleshooting Flow Chart continued ...
Page 55: ...SECTION 9 TROUBLESHOOTING 51 of 65 Troubleshooting Flow Chart continued ...
Page 57: ...SECTION 9 TROUBLESHOOTING 53 of 65 FIGURE 29 Troubleshooting Flow Chart BACnet ...
Page 65: ......