SECTION 6: C
LEARANCES
TO
C
OMBUSTIBLES
13 of 21
NOTE:
1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from
where the combustion chamber and the tube connect.
.
FIGURE 9: LEVEL REFLECTOR
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
CRV-B-2
4
20
48
20
11
51
122
51
CRV-B-4
4
20
48
20
11
51
122
51
CRV-B-6
4
20
48
20
11
51
122
51
CRV-B-8
4
20
48
20
11
51
122
51
CRV-B-9
4
36
60
36
11
92
153
92
CRV-B-10
4
36
60
36
11
92
153
92
CRV-B-12
4
36
60
36
11
92
153
92
CRV-B-12A
4
36
60
36
11
92
153
92
B
C
D
A
FIGURE 10: ONE SIDE REFLECTOR
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
CRV-B-2
4
12
56
20
11
31
143
51
CRV-B-4
4
12
56
20
11
31
143
51
CRV-B-6
4
12
56
20
11
31
143
51
CRV-B-8
4
12
56
20
11
31
143
51
CRV-B-9
4
12
60
42
11
31
153
107
CRV-B-10
4
12
60
42
11
31
153
107
CRV-B-12
4
12
60
42
11
31
153
107
CRV-B-12A
4
12
60
42
11
31
153
107
A
B
C
D
FIGURE 11: TWO SIDE REFLECTORS
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
CRV-B-2
4
12
56
12
11
31
143
31
CRV-B-4
4
12
56
12
11
31
143
31
CRV-B-6
4
12
56
12
11
31
143
31
CRV-B-8
4
12
56
12
11
31
143
31
CRV-B-9
4
12
60
12
11
31
153
31
CRV-B-10
4
12
60
12
11
31
153
31
CRV-B-12
4
12
60
12
11
31
153
31
CRV-B-12A
4
12
60
12
11
31
153
31
A
B
C
D
Summary of Contents for CORAYVAC CRVB04PN
Page 2: ......
Page 4: ......
Page 24: ...CRV SERIES FUEL CONVERSION INSTRUCTIONS 20 of 21 ...
Page 25: ...SECTION 8 THE ROBERTS GORDON CORAYVAC WARRANTY 21 of 21 2020 ...
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......