RLE Technologies WiNG-CO2 Quick Start Manual Download Page 2

Rotary Switch 

Setting

Altitude (ft) Altitude (m) CO2 Measurement 

Change (%)

9

4,500

1,373

22

A

5,000

1,525

24

B

6,000

1,830

28

C

7,000

2,135

32

D

8,000

2,440

36

E

9,000

2,745

40

F

10,000

3,050

44

c.  Set the Auto-Zero Function: When auto-zero is on, the sensor 

automatically re-calibrates every two weeks - the zero point of the CO2 

module resets to the lowest point detected during the past two weeks. 

This operation relies on there being a regular period of unoccupancy 

in the space, such as at nights or weekends, to ensure levels drop to 

around 400ppm. By default, each sensor is shipped with auto-zeroing 

turned ON.
•  Auto-Zero ON: The white jumper is in the leftmost “AUTO” 

position, covering the farthest left and middle pins.

•  Auto-Zero OFF: The jumper in the rightmost “OFF” position, 

covering the middle and farthest right pins. 

d. 

Configure the Zero Point in Fresh Air: The CO2 module must now be 

configured with the fresh air setting for its location. Expose the sensor 

to fresh air outside or in an unoccupied area for 5-10 minutes.

e.  The measurement interval on the WiNG-CO2 is by default set to 2 

minutes. This interval is configurable. If you’d like to change the 

measurement interval, you must do so now. Refer to the WiNG-CO2 

Measurement Interval Configuration Guide for complete instructions.

f. 

The initial configuration is complete, and now you must save the 

settings you’ve just programmed:
1.  Hold the push button on the top of the sensor. 
2.  While continuing to hold the button, reinstall the batteries. The 

LED will turn white to indicate that the sensor is in configuration 

mode.

3.  Continue to hold the push button. The LED will then turn green to 

indicate that configuration has completed successfully.

4.  Once the LED turns green, release the push button.

5.  Check the WiNG-MGR web interface or BMS and verify the sensor appears 

in the list of sensors connected to it. You may need to click the Sensor 

Discovery button in the WiNG-MGR web interface to allow the unit to find 

this new sensor. 

6.  Check the WiNG-MGR web interface or BMS to make sure the sensor status 

reports accurately.

LED

3.6V

Lithium

Batteries

Antenna

Circuit 

Board

Clip

L Brackets

Plastic 

Peg

Antenna Guides

Rotary 

Switch

Auto-Zero

Jumper

CO2 Sensor

Push 

Button

Plastic 

Peg

7.  Replace the lid, ensuring that the antenna is held in place by the antenna 

guides and feeds out the vent hole in the side of the enclosure. Do not pinch 

the antenna between the lid and the case.

Reviews: