www.rletech.com
17
970.484.6510
2
Getting Started
2.2.6 Update
Click the
Update
button to update the firmware installed on the selected F110. Updated
firmware files provided by RLE, add new features and enhance the web browser interface.
These firmware updates are available from RLE if firmware replacement is necessary.
Note
When obtaining the F110 Firmware Update file from the RLE Technologies website, be sure to
save the file instead of opening it from a web browser. After receiving the file, right-click the
F110 Firmware Update file and select “Properties.” If the F110 Firmware Update file has a “.zip”
extension, replace “.zip” with “.upd” before uploading the file with the Device Discovery Utility.
2.3. F110
Wiring
RLE recommends an 18AWG stranded copper wire for connection from each monitored point
to the terminal block (TB) connection on the F110 (8 Switched Sensors inputs only). RLE
recommends no more than 200 feet (60.9m) of wire at this specification. If longer runs are
needed, please contact RLE for application guidance.
2.3.1 Power Supply
Plug the wall adapter into the connection labeled
Power
. The wall adapter has a 6 foot
(18.82m) power cord. RLE recommends powering the F110 from a UPS supply to allow the
F110 to send alarm notification during a power outage.
Figure 2.3
5VDC Power Supply Connection
NEVER connect main power to the sensors or sensor cables.
W
ARNING
Summary of Contents for MONITORING F110
Page 1: ...Monitoring F110 User Guide...
Page 4: ...rletech com 4 970 484 6510 Notes...
Page 6: ...970 484 6510 6 rletech com Notes...
Page 8: ...rletech com 8 970 484 6510 Notes...
Page 10: ...970 484 6510 10 rletech com Notes...
Page 14: ...www rletech com 14 970 484 6510 1 System Overview Notes...
Page 34: ...www rletech com 34 970 484 6510 B Modbus Registers Notes...