15
!
"
3 #*$
3&*72
SETPOINT ASSIGNMENT
Select the display that the setpoint is to be assigned.
!
"
466
&.72
SETPOINT VALUE
Enter the desired setpoint value. Setpoint values can also be entered in the
Quick Programming Mode when the setpoint is configured as
(*$
in Module 3.
(See Module 2 for Exchange Parameter Lists explanation.)
!
"
*!
$%#72
SETPOINT TRACKING *
If a selection other than NO is chosen, then the value of the setpoint being
programmed (“n”) will track the entered selection’s value. Tracking means that
when the selection’s value is changed (in the Quick Programming Mode), the
“n” setpoint value will also change (or follow) by the same amount.
!
"
'!
$D.72
SETPOINT BOUNDARY TYPE
+)
activates the output when the assigned display value (
3&*72
) equals or
exceeds the setpoint value.
'!
activates the output when the assigned display
value is less than or equal to the setpoint.
!
"
*!
&$,72
SETPOINT STANDBY OPERATION *
Selecting
<(&
will disable low acting setpoints at a power up until the display
value crosses into the alarm “off” area. Once in the alarm “off” area, the
setpoint will function according to the configured setpoint parameters.
*
Factory Setting can be used without affecting basic start-up.
3 #*$
, #*$
# #*$
7;;;;;
to
;;;;;;
&.7@
*!
3#*$'- ,#*$'-
&.7>
##*$'-
&.7?
&.74
+)
'!
<(&
*!
!
"
*!
38$!72
COUNTER AUTO RESET *
This automatically resets the display value of the Setpoint Assignment (
3&*7
2
) counter each time the setpoint value is reached. This reset may be different
than the Counter’s Reset Action (x
%(&($
) in Module 1 or 5.
!
"
*!
%&-72
SETPOINT RESET WITH DISPLAY RESET *
Select
<(&
, so the setpoint output will deactivate (reset) when the Setpoint
Assignment (
3&*72
) counter display resets. The only exception is if the
assigned counter is reset by a Counter Auto reset generated by another setpoint.
!
"
6:66
$!8$72
SETPOINT TIME OUT *
This is the amount of time the output will activate once the count value
equals the setpoint value if the setpoint action is Timed Out.
6:66
to
;;:;;
seconds
ZErOAE
*!
CLdAS
ZErOAS
CLdAE
SELECTION
ACTION
NO
No auto reset.
ZErOAS
Reset to zero at the start of output activation.
CLdAS
Reset to count load value at the start of output activation.
ZErOAE
Reset to zero at the end of output activation. (
$!8$
action
only).
CLdAE
Reset to count load value at the end of output activation.
(
$!8$
action only).
<(&
*!
!
"
*!
%&3&72
SETPOINT RESET WHEN SPn+1 ACTIVATES *
Select
<(&
, so the setpoint output will deactivate (reset) when SPn +1
activates. (Example: SP1 deactivates when SP2 activates and SP4 when SP1
activates.) The last setpoint will wrap around to the first.
<(&
*!
!
"
*!
%&3(72
SETPOINT RESET WHEN SPn+1 DEACTIVATES *
Select
<(&
, so the setpoint output will deactivate (reset) when SPn +1
activates and then times out (deactivates). This function may only be used if the
SPn+1 is programmed for Setpoint Action of
$!8$
. (Example SP1 deactivates
when SP2 is activated and then times out.) The last setpoint will wrap around
to the first.
<(&
*!