RLC PAXC-1/8 Manual Download Page 1

GENERAL DESCRIPTION

The PAXC (PAX Counter Panel Meter) offers many features and

performance capabilities to suit a wide range of industrial applications. The
optional Plug-in Setpoint Alarm Cards allow the opportunity to configure the
meter for alarms if that is a requirement.

The PAXC meter accepts digital inputs from a variety of sources including

switch contacts, outputs from CMOS or TTL circuits and all standard RLC
sensors. The meter can accept directional, uni-directional or Quadrature signals
simultaneously.  The maximum input signal varies up to 34 KHz depending on
the count mode function configurations programmed. Each input signal can be
independently scaled to various process values.

The meter provides three different display indications. These include Counter

A, Counter B, and Counter C. Counter A and Counter B indicate the
corresponding input count value. Counter C indicates the sum or difference
between Counter A and Counter B values. Annunciators indicate which display
is being shown.

The front panel keys and three user inputs are programmable to perform

various meter functions. One function includes exchanging parameter lists,
allowing double the number of programmable setpoint, scale factor and count
load values.

The meter can have up to four setpoint outputs, determined by the Plug-in

cards. The Plug-in cards provide dual FORM-C relays (5 A), quad FORM-A
relays (3 A) or either quad sinking or quad sourcing open collector logic
outputs. The outputs can be assigned to any of the three displays. The outputs
can also be independently configured to suit a variety of control and alarm
requirements.

Once the meter has been initially configured, the parameter list may be

locked out from further modification entirely or setpoint, scale factor and count
load values can be made accessible. This lockout is possible through a security
code or user input.

The meter has been specifically designed for harsh industrial environments.

With a NEMA 4X/IP65 sealed bezel and extensive testing to meet CE
requirements, the meter provides a tough yet reliable application solution.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in this

literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.

Do not use this meter to directly command motors, valves, or other actuators

not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the unit.

1

MODEL PAXC-1/8 DIN COUNTER PANEL METER

!

6-DIGIT LED DISPLAY (Alternating 8 digits for counting)

!

DUAL COUNT QUAD INPUTS

!

UP TO 3 COUNT DISPLAYS

!

PROGRAMMABLE SCALE FACTORS

!

PROGRAMMABLE FUNCTION KEYS / USER INPUTS 

!

FOUR SETPOINT ALARM OUTPUTS (W/Plug-in card)

!

NEMA 4X/IP65 SEALED FRONT BEZEL

CAUTION: Read complete

instructions prior to installation

and operation of the unit.

CAUTION: Risk of electric shock.

DIMENSIONS  “In inches (mm)”

Note: Recommended minimum clearance (behind the panel) for 

mounting clip installation is 2.1” (53.4) H x 5.5” (140) W.

INTERNATIONAL  HEADQUARTERS

RED LION CONTROLS (UK)

20 Willow Springs Circle, York, Pa. 17402, (717) 767-6511 

Tapton Park, Chesterfield, Derbyshire S41 OTZ

Web site- http://www.redlion-controls.com      

ENGLAND   +44 1246 222122  FAX: +44 1246 221222

RED LION CONTROLS

BULLETIN NO.  PAXC-X
DRAWING NO.  LP0510
EFFECTIVE  3/00

Summary of Contents for PAXC-1/8

Page 1: ...initially configured the parameter list may be locked out from further modification entirely or setpoint scale factor and count load values can be made accessible This lockout is possible through a se...

Page 2: ...Expectancy 100 K cycles min at full load rating External RC snubber extends relay life for operation with inductive loads Response Time 5 msec nominal with 3 msec nominal release Time Accuracy 0 01 10...

Page 3: ...operly installed The unit is intended to be mounted into an enclosed panel Prepare the panel cutout to the dimensions shown Remove the panel latch and cardboard sleeve from the unit and discard the ca...

Page 4: ...When using the user inputs this jumper must be set before applying power The Main Circuit Board figure shows the location of the jumper and DIP switch The user input jumper determines signal logic fo...

Page 5: ...s conductors feeding motors solenoids SCR controls and heaters etc The cables should be run in metal conduit that is properly grounded This is especially useful in applications where cable runs are lo...

Page 6: ...s From Tach Generators Etc Two Wire Proximity Current Source Counter A Magnetic Pickup Current Sourcing Output Counter A Interfacing With TTL Counter A Current Sinking Output Counter A Switch or Isola...

Page 7: ...tions are disabled Throughout this document Programming Mode without Quick in front always refers to Full Programming MODULE ENTRY ARROW PAR KEYS The Programming Menu is organized into six modules The...

Page 8: ...edge when Input B is low Input B rising edge when Input A is low and Input B falling edge when Input A is high Subtracts Input A falling edge when Input B is high Input A rising edge when Input B is...

Page 9: ...B and any setpoint value assigned to Counter B The selection will also affect Counter B scale factor calculations 4 66666 3 COUNTER B SCALE FACTOR The number of input counts is multiplied by the scal...

Page 10: ...nput lockout Function keys should not be programmed for Module 2 is the programming for rear terminal user inputs and front panel function keys Three rear terminal user inputs are individually program...

Page 11: ...inhibits the displays configured as as long as activated maintained action 8 74 4 MOMENTARY EDGE RESET When activated momentary action the meter resets the displays configured as Momentary resets imp...

Page 12: ...e programmed for or See the following table Accessible only with the Setpoint Plug in card installed 3 COUNT LOAD A B C ACCESS LOCK OUT 3 The Scale Factor values can be programmed for or 3 SCALE FACTO...

Page 13: ...amount of pulses per unit of measurement Details on scaling calculations are explained at the end of Module 1 section 6 66664 to 7 to 4 6 4 6 64 9 Module 5 is the programming for Counter C For maximu...

Page 14: ...es this PARAMETER DESCRIPTION SETPOINT ACTION TIMED OUT 8 BOUNDARY 8 LATCH 3 LIt n Annunciators Yes Yes Yes OUt n Output Logic Yes Yes Yes SUP n Power Up State Yes Yes Yes SP n Setpoint Value Yes Yes...

Page 15: ...ter each time the setpoint value is reached This reset may be different than the Counter s Reset Action x in Module 1 or 5 72 SETPOINT RESET WITH DISPLAY RESET Select so the setpoint output will deact...

Page 16: ...HECK Corresponding plug in card installation related controlling parameter selected ERROR CODE 47 PRESS Reset key if unable to clear contact factory DISPLAY PARAMETER FACTORY SETTING USER SETTING A CN...

Page 17: ...Ct n HI OFF NOr NO NOr SETPOINT BOUNDARY TYPE SETPOINT POWER UP STATE SETPOINT OUTPUT LOGIC SETPOINT TRACKING SETPOINT ANNUNCIATORS tYP n SUP n OUt n trC n LIt n SP 1 FACTORY SETTING USER SETTING FACT...

Page 18: ...C Operating Mode Counter C Reset Action Counter C Decimal Position Counter C Scale Factor Counter C Scale Multiplier Counter C Count Load Value Counter C Reset at Power up B7 E 72 8 72 8 72 3 72 3 72...

Page 19: ...19 This page intentionally left blank...

Page 20: ...Circle York Pa 17402 717 767 6511 FAX 717 764 0839 Web site http www redlion controls com E mail sales redlion controls com RED LION CONTROLS UK Tapton Park Chesterfield Derbyshire S41 OTZ ENGLAND 44...

Reviews: