18 • T3A Transmitter
4. Connect the ground (WHITE) wire to the
GND
terminal.
5. Connect the RS-485 A (YELLOW) wire to the
A
terminal.
6. Feed the RS-485 cable through the power hub and into the controller and wire them to the
correct terminals as shown below.
Figure 6: Modbus Wiring
NOTE:
If an RKI controller is not used, the T3A can be connected to a Programmable Logic
Controller (PLC) for RS-485 Modbus data communications. For integration and
setup, refer to the Modbus Register Map found in Appendix C of this manual.