Termination Jumper
The M2A includes a 2-pin termination header (see Figure 4 on page 13) that is used when the M2A is
used in a Modbus system. Every M2A is supplied with a termination jumper (a jumper block) installed
onto this header. If the M2A is not used in a Modbus system, this jumper has no function. When the
M2A is installed in a Modbus system, this jumper must be installed in an M2A that is at the end of a
Modbus line. Any M2A in a Modbus system that is not at the end of a line must have the termination
jumper removed (see Figure 13 & Figure 14 below).
Figure 13: Multiple M2As in a Daisy Chain Configuration
ID = 125
Modbus
Master
Up to 128 M2As can be connected without a repeater
RS-485
RS-485
M2A
Termination
Jumper
Not Installed
M2A
Termination
Jumper
Not Installed
ID = 127
ID = 126
M2A
Termination
Jumper
Installed
ID = 128
M2A
Termination
Jumper
Not Installed
M2A
Termination
Jumper
Not Installed
ID = 1
Figure 14: Multiple M2As in a Two-Branch Configuration
ID = 4
ID = 127
M2A
Termination
Jumper
Installed
RS-485
ID = 128
Up to 128 M2As can be connected without a repeater
Modbus
Master
M2A
Termination
Jumper
Not Installed
M2A
Termination
Jumper
Not Installed
M2A
Termination
Jumper
Not Installed
M2A
Termination
Jumper
Not Installed
ID = 3
ID = 2
M2A
Termination
Jumper
Installed
ID = 1
RS-485