65-2662XL-04 M2A-XL Transmitter
Chapter 6: Gas Type Mode
•
35
4. When the desired target gas is on the display, press and release the ENTER button. The
display will ask
SAVE IT? YES/NO
.
5. To discard the gas type change, press and release the DOWN/NO button. The display will ask
DO OVER? YES/NO
. Press the DOWN/NO button. The display will ask
ABORT? YES/
NO
. Press the UP/YES button. The M2A-XL will return to normal operation without
changing the gas type.
To save the gas type, press and release the UP/YES button. The display will indicate
Gas
Type Updated
, the display will indicate the target gas and the detection range for a few
seconds, and then the M2A-XL will enter Configuration Mode automatically so that the
parameter settings in Configuration Mode can be verified or changed.
6. While in Configuration Mode press and release the ENTER button to accept the displayed
parameter setting and move to the next one. Use the UP/YES and DOWN/NO buttons to
adjust a setting. See “Chapter 5: Configuration Mode” on page 31 for a complete description
of Configuration Mode.
CL2
0 - 10.0 ppm
NH3
0 - 75.0 ppm
SO2
0 - 6.00 ppm
ASH3
0 - 1.50 ppm
H2S
0 - 50.0 ppm
CLO2
0 - 1.00 ppm
CLO2
0 - 3.00 ppm
NH3
0 - 500 ppm
NH3
0 - 200 ppm
HCN
0 - 15.0 ppm
CLO2
0 - 5.00 ppm
CL2
0 - 5.00 ppm
NH3
0 - 100 ppm
PH3
0 - 1.00 ppm
SIH4
0 - 15.0 ppm
OXYGEN
0 - 25.0% volume
Table 6: Gas Types
Gas Type
Choices
Detection Range