46
65-2643-05SS-4S M2A Transmitter Operator’s Manual
Registers 15 - 19
Registers 15 - 19 are the Gas Name ASCII String (NULL Terminated).
Registers 20 - 22
Registers 20 - 22 are the Gas Units String (NULL Terminated).
Register 23
Register 23 is the alarm 1 trigger.
0=Decreasing
1=Increasing
Register 24
Register 24 is the alarm 1 normal relay state.
0=Normally De-Energized
1=Normally Energized
Register 25
Register 25 is the alarm 1 relay reset.
0=Latching
1=Self-Resetting
Register 26
Register 26 is the alarm 1 ON delay.
Integer values are in seconds.
Register 27
Register 27 is the alarm 1 OFF delay.
Integer values are in seconds.
Register 28
Register 28 is the alarm 2 trigger.
0=Decreasing
1=Increasing
Register 29
Register 29 is the alarm 2 normal relay state.
0=Normally De-Energized
1=Normally Energized
Register 30
Register 30 is the alarm 2 relay reset.
0=Latching
1=Self-Resetting
Register 31
Register 31 is the alarm 2 ON delay.
Integer values are in seconds.
Register 32
Register 32 is the alarm 2 OFF delay.
Integer values are in seconds.