65-2394RK-CH4-4 Combustible Gas Transmitter • 3
Infrared LEL Detector
The infrared LEL detector is made up of a miniature infrared combustible gas LEL
detector housed and encapsulated in a pipe nipple. The pipe nipple has 3/4” NPT threads
on each end and a 1 1/4” hex that allows removal or installation of the detector with a
wrench. A porous flame arrestor that is coated with a hydrophobic film that repels liquids
is on one end of the detector and allows sample gas to enter the detector. Four color coded
leads, red, white, green, and black, extend from the other end of the detector. The leads
allow you to connect the detector to the amplifier.
Calibration Cup/Splash Guard
A calibration cup/splash guard is installed on the IR LEL detector. A fitting at the bottom
of the calibration cup/splash guard allows a length of tubing to be connected for
calibration and routed to a more easily accessible location. The calibration cup/splash
guard also protects the detector.
Amplifier
The amplifier is located in the amplifier junction box. The amplifier converts the electrical
output from the detector to a 4 to 20 mA signal that corresponds to the detection range
and transmits the signal to a gas monitoring controller. A foam gasket that orients the
amplifier and keeps it from rotating is installed on the bottom of the amplifier. A label on
the amplifier indicates the detector drive current. This drive current is factory set and is
dictated by the combustible gas to which the detector is calibrated. Consult RKI
Instruments, Inc. if you plan to change the calibration gas for the transmitter, for example
from a methane calibration to a hexane calibration. The amplifier includes the detector
terminal strip, controller terminal strip, span pot, zero pot, and test points (see Figure 1).
Controller Terminal Strip
The controller terminal strip is a three position plug-in style terminal strip located near the
top of the amplifier. Use the controller terminal strip to wire the combustible gas
transmitter to a controller.
Detector Terminal Strip
The detector terminal strip is a four position plug-in style terminal strip located below the
controller terminal strip. Use the detector terminal strip to connect the IR LEL detector to
the amplifier.
NOTE:
See “Wiring the Detector to the Amplifier” on page 6 for all wiring procedures
related to the transmitter.
Zero Pot
The zero pot is located in the upper left corner of the amplifier (see Figure 1). Use a small
flat blade screwdriver to turn the zero pot’s adjustment screw and adjust the amplifier’s
zero (fresh air) output during the start-up and calibration procedures. Turn the adjust-
ment screw clockwise to increase the zero output and counterclockwise to decrease the
zero output.
Span Pot
The span pot is located to the right of the zero pot (see Figure 1). Use a small flat blade
screwdriver to turn the span pot’s adjustment screw and adjust the amplifier’s gas
response output during the calibration procedure. Turn the adjustment screw clockwise to
increase the gas response and counterclockwise to decrease the gas response.
www.
GlobalTestSupply
.com
Find Quality Products Online at: