IMS01N02-E4
2
1. OUTLINE
One temperature control (TIO) module [basic type] enables
temperature control corresponding to two channels.
It has power supply and host communication terminals in
addition to temperature control input and output terminals.
The temperature control (TIO) module [basic type] can be
connected with the temperature control (TIO) module [extension
type], the digital input (DI) module and the digital output (DO)
module.
All data are set by communication. For details, see the
Module Type Controller SRX Communication
Instruction Manual (IMS01N01-E
)
.
Host computer
RS-485
Temperature
control module
[basic type]
X-TIO-A
Temperature
control module
[extension type]
X-TIO-B
Digital input
module
X-DI-A
Digital output
module
X-DO-A
Control
output
Digital
input
Digital
output
Measured
input
Control
output
Measured
input
Digital
input
Digital
output
SRX configuration example
2. PRODUCT CHECK
Before using this product, check each of the following:
•
Model code
•
Check that all of the accessories delivered are complete.
•
Check that there are no scratch or breakage in external
appearance (case, front panel, or terminal, etc).
X-TIO-A-
-
/ Y
(1) (2) (3) (4) (5) (6) (7)
(1) Type
A: Basic type (20 terminals)
(2) Input channel 1, (3) Input channel 2
K: TC K
J: TC J
T: TC T
S: TC S
R: TC R
A: TC PL
Ⅱ
N: TC N
E: TC E
W: TC W5Re/W26Re
B: TC B
D: RTD Pt100
P: RTD JPt100
1: 0 to 10 mV DC
2: 0 to 100 mV DC
3: 0 to 1 V DC
4: 0 to 5 V DC
5: 0 to 10 V DC
6: 1 to 5 V DC
7: 0 to 20 mA DC
8: 4 to 20 mA DC
(4) Control output 1, (5) Control output 2
M: Relay contact output
V: Voltage pulse output 0/12 V DC
4: 0 to 5 V DC
5 0 to 10 V DC
6: 1 to 5 V DC
7: 0 to 20 mA DC
8: 4 to 20 mA DC
(6) CT1 input, (7) CT2 input
N: None
P: CTL-6-P-N
S: CTL-12-S56-10L-N
3. PARTS DESCRIPTION
Terminal cover
Indication lamps
Address setting
switch
5
4
3
2
1
0
9 8 7
6
5
5
4
3
2
1
0
9 8 7
6
5
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVTNT4
Terminal cover
Joint connector
(Right-side)
Joint connector
(Left-side)
[Indication lamps]
z
FAIL/RUN
When normally:
A green lamp turns on (RUN)
When abnormally: A red lamp turns on (FAIL)
z
RX/TX
During data send and receive: A green lamp turns on
z
EVENT 1 to 4
Display various states by setting.
During ON state: A green lamp turns on
Display contents
Event 1 state, Event 2 state, Comprehensive event state,
Output state, Control state, Executing segment state,
Time signal state
4. COMMUNICATION SETTING
Set communication setting before mounting and wiring of SRX.
4.1 Module Address Setting
Set an address of module. For this setting, use a small blade
screwdriver.
5
4
3
2
1
0
9 8 7
6
5
5
4
3
2
1
0
9 8 7
6
5
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVTNT4
5
4
3
2
1
0
9 8 7
6
5
5
4
3
2
1
0
9 8 7
6
5
High-order digit
setting
(Set value
×
10)
Setting range: 0 to 99
(Factory set value: 00)
Low-order digit
setting
(Set value
×
1)
Address setting switch
•
For Modbus, the value obtained by adding “1” to
the set address corresponds to the address used
for the actual program.
•
Set the module address such that it is different to
the other addresses on the same line. Otherwise,
problems or malfunction may result.
Accessories
End Plate ................................................................... 2
Joint connector cover................................................. 2
Instruction Manual (IMS01N02-E4) ........................... 1
*