2-38
※
8 Time zone (UTC)
Data No.
Time zone (UTC)
0
-12:00
1
-11:00
2
-10:00
3
-09:00
4
-08:00
5
-07:00
6
-06:00
7
-05:00
8
-04:00
9
-03:00
10
-02:00
11
-01:00
12
+00:00
13
+01:00
14
+02:00
15
+03:00
※
9 SNTP manual calibration
Time is calibrated by SNTP function. (Only record stop)
The result of SNTP manual calibration can get by reading the same address "006E." (Status
response value)
●
The check on a Modbus protocol
①
Data receive only "0000H" or "AA01H". (The other command becomes a command error.)
②
When data is "0000H", "0000H" is set as a status response value.
(Manual calibration is not started.)
③
Calibrate when data is "AA01H", and the following conditions are satisfied.
・
The last status response value = 0000H
・
"SNTP function" of System is "ON".
・
Main record is not started.
Manual calibration is started. A status response value becomes "5500H".
※
Setting of SNTP uses what is beforehand set up by the recorder.
(Refer item 8.8 of Paperless Recorder Manual for SNTP function.)
●
The status response after a SNTP manual calibration reception.
A status response is as follows. (A communication state continues for a maximum of 30 seconds.)
5500H = Now communicating
5501H = Calibration success
5510H = Link down
5511H = DNS error
5512H = Address error
5513H = Time out
0000H = SNTP reception preparation completion (When 0000H is received.)
※
In order to check completion of action, please wait until a status response becomes except for
"5500H" or "0000H".
Data No.
Time zone (UTC)
16
+04:00
17
+05:00
18
+06:00
19
+07:00
20
+08:00
21
+09:00
22
+10:00
23
+11:00
24
+12:00
25
+13:00
26
+14:00
27
+04:30
28
+05:45
29
+05:30
30
+09:30