IMS01P10-E1
4
Set the module address such that it is different to
the other addresses on the same line. Otherwise,
problems or malfunction may result.
The previous page figure is open-style connector type.
The figure of micro-style connector type is the same as
a open-style connector type.
4.2 DeviceNet Communication Setting
Communication speed setting
Set the communication speed of DeviceNet. For this setting, use
a small blade screwdriver.
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVENT4
V
+
CA
N_
H
Dr
ai
n
CA
N_
L
V
−
N
O
D
E
AD
D
R
ESS
MS
D
LS
D
DR
FA
IL
RU
N
NS
MS
CO
M
. P
O
RT
Setting range: 0: 125 kbps
1: 250 kbps
2: 500 kbps
(Factory set value: 0)
DeviceNet communication
speed setting switch
(DR or RATE)
The above figure is open-style connector type. The
figure of micro-style connector type is the same as a
open-style connector type.
When any number between 3 and 9 is set, the
communication speed becomes “500 kbps.”
Number of communication data items when
conducting polling I/O communication and host
communication protocol setting
With the DIP switch 1 which there is on the left side of module,
set the number of communication data items when conducting
DeviceNet polling I/O communication, host communication
protocol
and internal communication mode.
Left side view (DeviceNet side)
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
ON
OFF
DIP switch 1
Terminal base
Module mainframe
1
2
Host communication (RS-485) speed
OFF OFF
2400
bps
ON OFF
9600
bps
OFF ON
19200
bps
ON ON
38400
bps
Factory set value: 38400 bps
4
5
Number of communication data items when
conducting polling I/O communication
OFF OFF
8
words
ON OFF
26
words
OFF ON
46
words
ON ON
100
words
Factory set value: 8 words
6
Host communication protocol selection
OFF RKC
communication
ON
Modbus
Factory set value: Modbus
7
Internal communication mode selection
OFF
DeviceNet communication mode
ON
Host communication (RS-485) mode
Factory set value: DeviceNet communication mode
Switch No. 3: OFF fixed (Don’t change this one)
Switch No. 8: OFF fixed (Don’t change this one)
Switch No. 1, 2, 6 and 7 are used for the setting
related to host communication on the DeviceNet
side. When used only for DeviceNet communication,
do not change the factory set values.
For the host communication of DeviceNet side, see the
Appendix B of
Module Type Controller SRV
DeviceNet Communication Instruction Manual
(IMS01P11-E ).
4.3 Host Communication Setting
(temperature control side)
With the DIP switch 2 which there is on the right side of module,
set
the communication speed, data bit configuration, protocol,
and
termination resistor of internal data bus
for host communication of
temperature control side
.
Right side view (Temperature control side)
DIP switch 2
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
ON
OFF
Terminal base
Module mainframe
1
2
Host communication (RS-485) speed
OFF
OFF
2400 bps
ON
OFF
9600 bps
OFF
ON
19200 bps
ON
ON
38400 bps
Factory set value: 38400 bps
3
4
5
Data bit configuration
ON
OFF
OFF Data 8-bit, without parity, Stop 1-bit
Factory set value: Data 8-bit, without parity, Stop 1-bit
6
Host communication protocol selection
OFF
RKC communication
ON
Modbus
Factory set value:
Modbus
Switch No. 7: OFF fixed (Don’t change this one)
Switch No. 8: OFF fixed (Don’t change this one)
When connecting two or more modules (V-TIO-A,
V-TIO-B, V-TIO-C or V-TIO-D) to the module (V-TIO-J
or V-TIO-K), match all of the switch No. 1 to 6
settings with the internal settings of the module
(V-TIO-J or V-TIO-K).
When no host communication terminals are used, it
is not necessary to set the DIP switch 2.
For host communication using host communication
terminals, see the
Appendix B of
Module Type
Controller SRV DeviceNet Communication
Instruction Manual (IMS01P11-E )
and the
Module
Type Controller SRV Communication Instruction
Manual (IMS01P01-E )
.