RKC INSTRUMENT V-TIO-J Instruction Manual Download Page 4

IMS01P10-E1

 

 

Set the module address such that it is different to 
the other addresses on the same line. Otherwise, 
problems or malfunction may result. 

 

The previous page figure is open-style connector type. 
The figure of micro-style connector type is the same as 
a open-style connector type. 

 

4.2 DeviceNet Communication Setting 

 

Communication speed setting 

Set the communication speed of DeviceNet. For this setting, use 
a small blade screwdriver.

 

 

FAIL/RUN 
RX/TX 
EVENT1 
EVENT2 
EVENT3 
EVENT4 

V

+

 

CA

N_

Dr

ai

CA

N_

V

 

N

O

D

E

 AD

D

R

ESS 

MS

D

 

LS

D

 

DR 

FA

IL

 

RU

NS

 

MS

 

CO

M

. P

O

RT 

Setting range:  0: 125 kbps 

1: 250 kbps 

2: 500 kbps 

(Factory set value: 0) 

DeviceNet communication 

speed setting switch

(DR or RATE) 

 

 

The above figure is open-style connector type. The 
figure of micro-style connector type is the same as a 
open-style connector type. 

 

When any number between 3 and 9 is set, the 
communication speed becomes “500 kbps.”

 

 

 

Number of communication data items when 
conducting polling I/O communication and host 
communication protocol setting 

With the DIP switch 1 which there is on the left side of module, 
set the number of communication data items when conducting 
DeviceNet polling I/O communication, host communication 
protocol

 

and internal communication mode. 

 

 

Left side view (DeviceNet side) 

1 2 3 4 5 6 7 8 

ON 

1 2 3 4 5 6 7 8 

ON 

ON

OFF

DIP switch 1 

Terminal base 

Module mainframe 

 

 

Host communication (RS-485) speed

 

OFF OFF 

2400 

bps 

ON OFF 

9600 

bps 

OFF ON 

19200 

bps 

ON ON 

38400 

bps 

Factory set value:  38400 bps 

 

Number of communication data items when 

conducting polling I/O communication 

OFF OFF  

words 

ON OFF  

26 

words 

OFF ON  

46 

words 

ON ON  

100 

words 

Factory set value:  8 words 

 

Host communication protocol selection

 

OFF RKC

 communication

 

ON 

Modbus

 

Factory set value:  Modbus 

 

 

Internal communication mode selection

 

OFF

DeviceNet communication mode 

ON

Host communication (RS-485) mode 

Factory set value:  DeviceNet communication mode 

 

Switch No. 3: OFF fixed (Don’t change this one) 
Switch No. 8: OFF fixed (Don’t change this one) 

 

Switch No. 1, 2, 6 and 7 are used for the setting 
related to host communication on the DeviceNet 
side. When used only for DeviceNet communication, 
do not change the factory set values. 

 

For the host communication of DeviceNet side, see the

 

Appendix B of

 

Module Type Controller SRV 

DeviceNet Communication Instruction Manual 
(IMS01P11-E ).

 

 

 

4.3 Host Communication Setting   

(temperature control side) 

With the DIP switch 2 which there is on the right side of module, 
set 

the communication speed, data bit configuration, protocol, 

and 

termination resistor of internal data bus

 for host communication of

 

temperature control side

.

 

 

Right side view (Temperature control side) 

DIP switch 2 

1 2 3 4 5 6 7 8

ON 

1 2 3 4 5 6 7 8

ON 

ON

OFF

Terminal base 

Module mainframe

 

 

Host communication (RS-485) speed 

OFF

OFF

2400 bps 

ON

OFF

9600 bps 

OFF

ON

19200 bps 

ON

ON

38400 bps 

Factory set value:  38400 bps 

 

Data bit configuration 

ON

OFF

OFF Data 8-bit, without parity, Stop 1-bit 

Factory set value:  Data 8-bit, without parity, Stop 1-bit 

 

Host communication protocol selection 

OFF

RKC communication 

ON

Modbus 

Factory set value: 

Modbus

 

 

Switch No. 7: OFF fixed (Don’t change this one) 
Switch No. 8: OFF fixed (Don’t change this one) 

 

When connecting two or more modules (V-TIO-A, 
V-TIO-B, V-TIO-C or V-TIO-D) to the module (V-TIO-J 
or V-TIO-K), match all of the switch No. 1 to 6 
settings with the internal settings of the module 
(V-TIO-J or V-TIO-K). 

 

When no host communication terminals are used, it 
is not necessary to set the DIP switch 2. 

 

For host communication using host communication 
terminals, see the 

Appendix B of

 

Module Type 

Controller SRV DeviceNet Communication 
Instruction Manual (IMS01P11-E )

 and the 

Module 

Type Controller SRV Communication Instruction 
Manual (IMS01P01-E )

 

 

 

 

 

Summary of Contents for V-TIO-J

Page 1: ...panel All high voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions described in this manual...

Page 2: ...K K02 0 to 400 C KB9 32 to 752 F K04 0 to 800 C KB8 32 to 1472 F K16 200 to 1372 C KB7 328 to 2501 F K09 0 0 to 400 0 C KC2 32 0 to 752 0 F K35 200 0 to 400 0 C KC1 328 0 to 752 0 F J J02 0 to 400 C J...

Page 3: ...idly NS or NET Network status Network is operating normally but communications have not yet been established A green lamp flashes Network is operating normally communications established A green lamp...

Page 4: ...ommunication mode selection OFF DeviceNet communication mode ON Host communication RS 485 mode Factory set value DeviceNet communication mode Switch No 3 OFF fixed Don t change this one Switch No 8 OF...

Page 5: ...igure of micro style connector type is the same as a open style connector type Depth in connector mounting Conduct installation in consideration of the sizes of the connector and cable when connector...

Page 6: ...esistance between the three lead wires To avoid noise induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment If there is electrical noi...

Page 7: ...Number of inputs 2 points Isolated between each channel Thermocouple input Voltage low input Not isolated between each channel RTD input Voltage high input Current input Input type Thermocouple K J T...

Page 8: ...nnection T branch connection Terminating resistor 121 1 4 W is necessary Communication speed 125 kbps 250 kbps or 500 kbps Error control CRC error Node address MAC ID duplication check Maximum number...

Reviews: