[SRVP-01] Front-screw type 

[SRVP-02] Side-screw type

Stripping length 

10 mm 

Stranded wire size: 
 

0.2 to 2.5 mm

 (AWG 

24-12) 

Recommended tightening 
torque:  0.5 to 0.6 N

 

(5 to 6 kgf

cm) 

Stripping length

7 mm 

Stranded wire size: 
 0.2 

to 

2.5 

mm

 (AWG 

24-12) 

Recommended tightening 
torque: 0.5 to 0.6 N

 

(5 to 6 kgf

cm) 

 

 
 

7. SPECIFICATIONS 

 

Inputs 

Number of inputs: 

2 points 
Isolated between each channel: 
  Thermocouple input, Voltage (low) input 
Not isolated between each channel: 
  RTD input, Voltage (high) input,   
 Current input 

Input type: 

 

Thermocouple 

K, J, T, S, R, E, B, N (JIS-C1602-1995) 

  

PLII 

(NBS) 

  

W5Re/W26Re 

(ASTM-E988-96) 

 

RTD Pt100, 

JPt100 

 

Voltage (low) 

0 to 100 mV 

 

Voltage (high) 

0 to 5 V, 0 to 10 V, 1 to 5 V 

 

Current 

0 to 20 mA, 4 to 20 mA 

 

Sampling cycle: 

500 ms 

PV bias: 

Input span to 

+

Input span 

CT input: 

2 points 
 

0.0 to 30.0 A (CTL-6P-N) or 

 

0.0 to 100.0 A (CTL-12-S56-10L-N) 

 

 

Outputs 

Number of outputs: 

2 points   
(Isolated between input and output, and 
between output and power supply) 

Output type: 

Relay contact: 

250 V AC, 3 A (Resistive load)   

 1a 

contact 

 

Electrical life 300,000 times or more   

 (Rated 

load) 

Voltage pulse: 

0/12 V DC   

 

(Load resistance 600 

 or more) 

Current: 

0 to 20 mA DC, 4 to 20 mA DC 

 

(Load resistance 600 

 or less) 

Voltage: 

0 to 5 V DC, 0 to 10 V DC, 1 to 5 V DC 

 

(Load resistance 1 k

 or more) 

 

 

Control action 

Number of controls: 

2 points 

Control method: 

Brilliant PID control 
Reverse action or direct action is 
selectable (Specify when ordering) 
Heat/cool control is selectable   
(Specify when ordering) 

Additional function: 

Autotuning function 

 

Events 

Number of events: 

2 points/channel 

Event type: 

Temperature event: 
 

Deviation high, Deviation low, 

 

Deviation high/low, Band,   

 

Process high, Process low 

Heater break alarm,   
Control loop break alarm,   
Burnout, Temperature rise completion 

 

 

Option 

 

Event input 

Number of inputs: 

1 point 

Input type: 

Dry contact input 

Input voltage: 

24 V DC (Rated) 

Input current: 

Approx. 6 mA 

Input details: 

Control RUN/STOP,   
Event interlock release   
(Specify when ordering) 

 

Event output 

Number of outputs: 

2 points 

Output type: 

Relay contact output 
250 V AC, 1 A (Resistive load) 
1a contact 
Electrical life 300,000 times or more   
 (Rated 

load) 

Output details: 

Temperature event, Heater break alarm, 
Control loop break alarm, Burnout, 
Temperature rise completion 
(Specify when ordering) 

 

 

Communications 

Communication interface: Based on RS-485, EIA standard 
Communication protocol:  RKC communication   

(ANSI X3.28 subcategory 2.5, A4) 
or Modbus 

Connection: Internal 

bus 

 

 

Others 

Power supply voltage:  24 V DC 

(The power is supplied from temperature 
control module [basic type].) 

Power supply voltage range: 

21.6 V DC to 26.4 V DC 

Current consumption:  With event input/output (option): 

 

120 mA max./module 

Without event input/output (option): 
 

90 mA max./module 

Allowable ambient temperature range: 

10 to 

+

50 

°

Allowable ambient humidity range: 

5 to 95 %RH (Non condensing) 
Absolute humidity:   
MAX.W.C 29.3 g/m

3

 dry air at 101.3 kPa 

Installation environment conditions: 

Indoor use   
Altitude up to 2000 m 

Weight: 

With event input/output (option): 
 

Approx. 180 g 

Without event input/output (option): 
 

Approx. 170 g 

 

Summary of Contents for V-TIO-B

Page 1: ...als must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions described in this manual should be taken to avoid damage to the instrument or equipment All wiring must be in accordance with local codes and regulations All wiring must be completed before power is turned on to prevent electric shock instrument failure or incorrect action The power mus...

Page 2: ...7 0 to 400 C DC5 32 to 752 F D33 0 to 850 C DC4 32 to 1562 F D16 0 0 to 400 0 C DC7 32 0 to 752 0 F D28 200 0 to 400 0 C DC6 328 0 to 752 0 F JPt100 P17 0 to 400 C PC5 32 to 752 F P23 0 to 600 C PC4 32 to 1112 F P16 0 0 to 400 0 C PC7 32 0 to 752 0 F P28 200 0 to 400 0 C PC6 328 0 to 752 0 F Voltage current input Code Type Code Type Voltage 201 0 to 100 mV DC 401 0 to 5 V DC 501 0 to 10 V DC 601 1...

Page 3: ...n the Modbus communication protocol is selected this setting becomes invalid Factory set value Data 8 bit without parity Stop 1 bit 6 Protocol selection OFF RKC communication ON Modbus Factory set value Specify when ordering Switch No 7 and 8 must be always OFF Do not set to ON When two or more modules are connected on the same communication line the DIP switch settings switch 1 to 6 of all module...

Page 4: ...until locked and that a mounting hole appears 2 Prepare one mounting bracket per module B sold separately KSRX 55 and then insert it in the rear of the terminal board at top of the module until locked but a mounting hole does not disappear 3 Mount each module directly on the panel with screws which are inserted in the mounting holes of the top and bottom mounting brackets Recommended tightening to...

Page 5: ...output and Control output 2 corresponds to the cooling output Terminal No 11 is not used Use the solderless terminal appropriate to the screw size M3 6 3 Pin Layout of Connector When there is the event input output 1 6 Event input output connector socket Circuit configuration 24 V DC 1 2 3 DI 4 5 6 Load DO1 DO2 Load 6 4 Attention in Connector plug Wiring Use the following connector plug as that co...

Page 6: ...ge 0 to 5 V DC 0 to 10 V DC 1 to 5 V DC Load resistance 1 kΩ or more Control action Number of controls 2 points Control method Brilliant PID control Reverse action or direct action is selectable Specify when ordering Heat cool control is selectable Specify when ordering Additional function Autotuning function Events Number of events 2 points channel Event type Temperature event Deviation high Devi...