4. WIRING 

 
 
 
 
 
 

 

 

 

Wiring Cautions 

To avoid noise induction, keep communication signal wire away 
from instrument power line, load lines and power lines of other 
electric equipment.

 

 

 

Method to connect 

(1) For loader communication 

 

 

Connected to loader 

communication connector of

the controller 

(FB400/FB900) 

Connected to USB 
port of a personal 
computer 

USB cable 

Loader communication 

cable (W-BV-01) 

[Option] 

USB 

communication 

 converter

 

COM-K 

Connected to USB 

connector 

Connected to loader 
communication connector 

 

 

While loader communication is being performed,     
DO NOT turn on or off the instrument power supply  
(e.g. FB400/FB900). The loader may be stopped. 
Please refer to our web site http://www.rkcinst.com for 
how to communicate to FB series with a COM-K.

 

 

The COM-K can be connected at either the power turned ON 
or OFF of the controller. When the power of the controller is 
turned off, COM-K supplies power to the controller after 
approximately 2 seconds. 

 

While the power is being supplied from the COM-K, the 

−−−−

” is displayed on the PV/SV display of the controller. 

 

(2) For RS-485/RS-422A communication 

 

 

RS-485/RS-422A

Connected to USB 
port of a personal 
computer 

USB cable 

Connected to 

communication terminals

of controller 

(Example: FB400/FB900)

USB 

communication 

 converter

 

COM-K 

Connected to USB 

connector 

Connected to  

RS-485/RS-422A 

communication 

connector 

 

 

Connector pin configuration 

 

1  2 3 4  5 

RS-485/RS-422A 

communication 

connector 

 

 

[RS-485] [RS-422A] 

Pin No.  Signal name  Symbol 

 

Pin No.

 

Signal name Symbol

Signal ground 

SG 

 

Signal ground

SG 

Send data/ 

Receive data 

T/R (A)   

Send data 

T (A)

Send data/ 

Receive data 

T/R (B)   

Send data 

T (B)

4 * 

Unused 

 

 

Receive data

R (A)

5 * 

Unused 

 

 

Receive data

R (B)

* Do not connect wires to 4 and 5 pins. Malfunction may result.

 

 

Connection diagram 

 

Shielded twisted 

pair wire 

T/R (A)
T/R (B)

1

SG

2

R

Controller

(Example: FB400/FB900)

COM-K 

R

R: Termination resistors 120 

 1/2W



5


T/R (A)

T/R (B)

25 SG
26 
27 

RS-485/RS-422A

communication 

connector 

Communication terminals

(communication 1 side)

[RS-485]

 

 

Shielded twisted 

pair wire 

T (A)

R (A)

1

SG

2

Controller

(Example: FB400/FB900)

COM-K 



5

T (A) 

R (A) 

25 SG
26 
27 

RS-485/RS-422A

communication 

connector

Communication terminals 

(Communication 1 side) 

[RS-422A]

28 

29 

T (B) 

R (B) 

T (B)

R (B)

 

 

Attention in connector wiring 

• 

The lead wires use the stranded wire. 

• 

Use the stranded wire from size 0.25 to 0.5 mm

2

 (AWG 26-20). 

• 

Stripping length is as follows. 

 

8 mm (Stripping length) 

Conductor cross section: 

0.25 to 0.5 mm

2

 (AWG 26-20) 

Connector type: FK-MC 0,5/5-ST-2,5

 

(Products by Phoenix contact Ltd.)

 

 

Installation of USB device driver 

Installs an USB device driver in a personal computer before use. 

1. 

Connect COM-K to USB port of a personal computer. 

2. 

Install an USB device driver from attached floppy disk according 

to an on screen instruction.

 

 

5. SPECIFICATIONS

 

USB function 

Interface: 

Based on USB Ver. 2.0 

Communication speed:  Full speed (12 Mbps) 

Connection: 

Connected by universal USB cable 

(Mini-B connector) 

Power source method:  Bus power (The power is supplied from the 

USB port on the personal computer side) 

Compatible OS: 

Windows XP/ 2000 Professional/ Me/ 

98 Second Edition

 

 

Communication function 

Interface: 

Based on RS-485, EIA standard 

 

Based on RS-422A, EIA standard 

Connection 

method:  2-wire system, half-duplex multi-drop 

connection (RS-485) 

4-wire system, half-duplex multi-drop 

connection (RS-422A) 

Synchronous method:  Half-duplex start-stop synchronous type 

Communication speed:  2400  bps, 4800 bps, 9600 bps, 19200 bps, 

38400 bps 

Data bit configuration:  Start bit: 

Data bit: 

7 or 8 

Parity bit:  Without, Odd or Even 

Stop bit: 

1 or 2 

Protocol: 

Protocol depends on application of the 

personal computer side 

Number of connecting controllers 

 

Maximum 31 controllers (RS-485, RS-422A) 

Termination resistor: 

Externally connected (RS-485) 

 

General specifications 

Power supply voltage:  5 V DC 

±

%

 (Supplied by USB bus cable) 

Current consumption:  150 mA max. (Loader communication) 

60 mA max. (RS-485/RS-422A communication) 

Allowable ambient temperature range: 

10 to 

+

50 

°

Allowable ambient humidity range: 

5 to 95 %RH (Non condensing) 

Absolute humidity:   

MAX.W.C 29 g/m

3

 dry air at 101.3 kPa 

Weight: 

Approx. 40 g

 

 

 

 

 

 

To prevent electric shock or instrument failure, turn off the 
power before connecting or disconnecting the instrument 
and peripheral equipment.

 

!

 

WARNING 

 

 

 