24V AC/DC INPUT CIRCUIT BOARD

(shown without detector wiring harness)

120V AC INPUT CIRCUIT BOARD

(shown without detector wiring harness)

Selective Hold Open Range

These units feature hold open (as shipped) starting at 85°. These units will hold open at virtually any degree of door opening from
85° to 180°. The hold open starting point may be changed (increased or decreased) by loosening the selective hold open cam
screw, rotating the cam to the desired new starting point and re-tightening the cam screw.

Setting

Door

Angle

G     H     J     K     L      M

15°   30°  45°  60°  90°  135°

16

17

15

cont

Page 4

For complete wiring instructions, refer to

“Wiring Instructions” 80-9342-0902-015.

5/32” wrench

provided

5/32” wrench

provided

120VAC

24VAC

24VDC

Voltage

Current

120V

24V

24V

132V Max
102V Min

26.4V Max
20.4V Min

26.4V Max
20.4V Min

.036 Amps

.059 Amps

.074 Amps

Detector

26.4V Max
20.4V Min

0.034 Amps

24V

Selective Hold-

Open

Connection

Selective Hold-Open

Connection

Solenoid

Connection

Solenoid

Connection

120V AC

Power Input

Test Switch

Test Switch

Fuse

PTO125V

(125V / 1/2A)

Fuse

PTO125V

(125V / 1/2A)

24V AC/DC

Power Input

4-Pin Connector

Of Detector

Wiring Harness

4-Pin Connector

Of Detector

Wiring Harness

An ASSA ABLOY Group Co.

3000 Highway 74 East  •  Monroe, NC 28112

Tel:

ww.r ixson.com

(800)-457-5670

w

Rixson ® is a registered trademark of Yale Security Inc., an ASSA ABLOY
Group company. Copyright © 2009 Yale Security Inc., an ASSA ABLOY
Group company. All rights reserved. Reproduction in whole or in part
without the express written permission of Yale Security Inc. is prohibited.

80-9372-0095-015 (02-09)