![Rixson DE 6 PULL Installation Instructions Download Page 4](http://html1.mh-extra.com/html/rixson/de-6-pull/de-6-pull_installation-instructions_1466325004.webp)
24V AC/DC INPUT CIRCUIT BOARD
(shown without detector wiring harness)
120V AC INPUT CIRCUIT BOARD
(shown without detector wiring harness)
Selective Hold Open Range
These units feature hold open (as shipped) starting at 85°. These units will hold open at virtually any degree of door opening from
85° to 180°. The hold open starting point may be changed (increased or decreased) by loosening the selective hold open cam
screw, rotating the cam to the desired new starting point and re-tightening the cam screw.
Setting
Door
Angle
G H J K L M
15° 30° 45° 60° 90° 135°
16
17
15
cont
Page 4
For complete wiring instructions, refer to
“Wiring Instructions” 80-9342-0902-015.
5/32” wrench
provided
5/32” wrench
provided
120VAC
24VAC
24VDC
Voltage
Current
120V
24V
24V
132V Max
102V Min
26.4V Max
20.4V Min
26.4V Max
20.4V Min
.036 Amps
.059 Amps
.074 Amps
Detector
26.4V Max
20.4V Min
0.034 Amps
24V
Selective Hold-
Open
Connection
Selective Hold-Open
Connection
Solenoid
Connection
Solenoid
Connection
120V AC
Power Input
Test Switch
Test Switch
Fuse
PTO125V
(125V / 1/2A)
Fuse
PTO125V
(125V / 1/2A)
24V AC/DC
Power Input
4-Pin Connector
Of Detector
Wiring Harness
4-Pin Connector
Of Detector
Wiring Harness
An ASSA ABLOY Group Co.
3000 Highway 74 East • Monroe, NC 28112
Tel:
ww.r ixson.com
(800)-457-5670
w
Rixson ® is a registered trademark of Yale Security Inc., an ASSA ABLOY
Group company. Copyright © 2009 Yale Security Inc., an ASSA ABLOY
Group company. All rights reserved. Reproduction in whole or in part
without the express written permission of Yale Security Inc. is prohibited.
80-9372-0095-015 (02-09)