Hinge (pull) side of door mounting
Double Egress Arm
and Slide Track
Master Unit
Models
DE 6 PULL
Selective Multipoint
Hold Open
AN INCORRECTLY INSTALLED OR IMPROPERLY
ADJUSTED DOOR CLOSER CAN CAUSE
PROPERTY DAMAGE OR PERSONAL INJURY.
THESE INSTALLATION INSTRUCTIONS SHOULD
BE FOLLOWED TO AVOID THE POSSIBILITY OF
MISAPPLICATION OR MISADJUSTMENT.
CA
UTION
CA
UTION
Combination Door Closer-Holder and Releasing
Device With Integral Smoke Detector
All dimensions are in inches and (millimeters) unless otherwise noted.
Backplate
Mtg Screw (5)
Arm Screw
Track Mtg
Screw (3)
Cover
Backplate
Hook-up Board
Main Arm
Slide Track
Concealed Wired Unit Shown
Cover Mtg
Screw (3)
RH - Right Hand Door
LHR - Left Hand Reverse
Left Hand Door - LH
Right Hand Reverse - RHR
Installation Instructions
80-9372-0095-015 (02-09)
Selective Hold Open
Cam & Switch
Assembly
Closer/Holder
Test Switch
Access Tube
Slide Assembly
Smoke Detector
Smoke Detector Reset Button
9/32” (7 mm);
3/8” (9.5 mm) dia. x
3/8” (9.5 mm) deep on
door opposite to closer
Standard
Optional
Through-bolts and
grommet-nuts
All
Preparation for Fasteners
Door or Frame
Fasteners
Drill-Sizes
1/4” - 20 machine
screw
Metal
Drill: #7 (0.201” dia.)
Tap: 1/4” - 20
Sleeve nuts and bolts
Hollow
Metal
9/32” (7 mm) through;
3/8” (9.5 mm) door face
opposite to closer
Aluminum
or Wood
3/8” (9.5 mm) through
Use of an auxiliary door stop, by
others, is required.
NOTE: For special applications a separate door and frame preparation template is packed with these
instructions. Use this instruction sheet for installation sequence and closer adjustments only.
For wiring, see “Wiring Instructions” part number
.
80-9342-0902-015 (02-09)
Requirements:
Units are handed. Hand of unit and hand of door must be the
same.
Door must be hung on butt hinges or ¾” (19) offset pivots.
Door thickness must be 1¾” (44) minimum 2¼” (64) maximum.
Door must swing freely through the entire opening and closing
cycle before beginning the installation procedure.
Frame face must be a minimum of 2” (51).
Ceiling clearance must be a minimum of 4” (102).
Power input to unit must be of the same voltage as that stated
on the unit.
Unit to be mounted on interior of building in dry environment,
maximum humidity of 95%.
See NFPA70 for wiring requirements and NFPA72 for alarm
system requirements.
Ceiling Line
2
(51)
4
(102)
Min
Min
Note:
Only for
hinge side
frame reveals
of 1/8” to 3”
(3mm to
76mm)